Table 5-9
Error Responses
Error Description
Status
Health
Error Status
The input value lies outside the
given limits
OK
Yes
Channel not connected
OK
No
Application and Setting Notes
Parameter: Unit
•
Default setting
(_:13111:103) Unit
=
°C
You use the setting
Unit
to specify which physical unit of measurement the measured values represent. The
possible setting values are listed in the settings table.
Parameter: Conversion factor
•
Default setting
(_:13111:104) Conversion factor
=
100
The
Conversion factor
setting allows you to set the conversion factor for the measuring transducer.
Parameter: Resolution
•
Default setting
(_:13111:108) Resolution
=
0.1
The
Resolution
setting is used to specify the measured value resolution.
Parameter: Range active
•
Default setting
(_:13111:107) Range active
=
false
If you do not activate the
Range active
setting (no x in the check box), the function operates over the
range -24 mA to +24 mA. The setting of the range for the scaled value goes from a usable range of -20 mA to
+20 mA.
If you activate the
Range active
setting, then 4 additional settings
Upper limit
,
Upper limit -
Sensor
,
Lower limit
, and
Lower limit - Sensor
appear.
Parameter: Upper limit, Lower limit, Upper limit - Sensor and Lower limit - Sensor
•
Default setting
(_:13111:105) Upper limit
=
20.000 mA
•
Default setting
(_:13111:109) Upper limit - Sensor
=
100
•
Default setting
(_:13111:106) Lower limit
=
4.000 mA
•
Default setting
(_:13111:110) Lower limit - Sensor
=
100
If you activate the
Range active
setting, then 4 additional settings
Upper limit
,
Lower limit
,
Upper
limit - Sensor
, and
Lower limit - Sensor
appear. The setting
Upper limit - Sensor
is the
calculated measured value if the input current corresponds to the value in the
Upper limit
setting. The
setting
Lower limit - Sensor
is the calculated measured value if the input current corresponds to the
value in the
Lower limit
setting.
The following settings and information table shows only 1 of the 12 channels, as the setting possibilities of
the 12 channels do not differ.
5.7.3.6
Function-Group Types
5.7 Function-Group Type Analog Units
260
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...