Binary Output Signal
Description
(_:5161:319) Time
delay different
Signal
Time delay different
indicates that the threshold value for asym-
metrical transit times has been exceeded. The setting value results from the
setting value of the parameter
(_:5161:110) Difference Tx and Rx
time
.
(_:5161:320) Time
delay jump
Signal
Time delay jump
indicates that the data transit times changed
abruptly. This is caused by switching the communication path in the communica-
tion network.
(_:5161:321) PI
synchronized
Signal
PI synchronized
indicates that the protection-interface connection is
synchronized with the opposite end.
(_:5161:340) Tele-
gram lost
Signal
Telegram lost
indicates that an expected telegram has failed to arrive
or a faulty telegram has been received.
If you would like to allocate the communications failures or faults to other events,
move the signal
Telegram lost
temporarily into the operational log. Such
events can be switching operations in the primary system or operations on the
components of the communication network.
Note: If the signal is constantly routed, the operational log can overflow. Siemens
recommends routing the signal only for clarification of faults.
Measured Values of the Protection Interface
The protection interface provides the following measured value to diagnose the protection interface commu-
nication:
Measured Value
Description
(_:5161:308) Tx
tel/h
Telegrams sent during the last hour
(_:5161:309) Rx
tel/h
Telegrams received during the last hour
(_:5161:310) Tx
tel/min
Telegrams sent during the last minute
(_:5161:311) Rx
tel/min
Telegrams received during the last minute
(_:5161:312) Tx
err/h
Transmission failure rate during the last hour
(_:5161:313) Rx
err/h
Receive error rate during the last hour
(_:5161:314) Tx
err/min
Transmission failure rate during the last minute
(_:5161:315) Rx
err/min
Receive error rate during the last minute
(_:5161:325)
Aver.Δt
Mean signal-transit time (average value of the transit time in transmission and
reception direction divided by 2, without GPS synchronization)
(_:5161:326) Rec.
Δt
Signal-transit time in reception direction (with GPS synchronization)
(_:5161:327) Sen.
Δt
Signal-transit time in transmission direction (with GPS synchronization)
(_:5161:334)
Miss.tel/min
Number of telegram failures within the last minute
(_:5161:335)
Miss.tel/h
Number of telegram failures within the last hour
(_:5161:336)
Miss.tel/d
Number of telegram failures within the last day
System Functions
3.5 Protection Communication
SIPROTEC 5, High-Voltage Bay Controller, Manual
121
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...