You can log off the device as follows:
•
Via the on-site operation panel
•
Via a communication interface using the
Device logoff
(
_:319
) controllable
•
Via the binary inputs, general:
>Device funct.logoff on
(
_:507
) or
>Dev. funct.logoff off
(
_:508
)
You can find the controllable and the binary inputs in the DIGSI 5 project tree under Name of the
device→Information routing in the working area in the General block.
During the log-off process, the device checks whether all conditions for a logoff have been met. If the condi-
tions for the log off have not been met, the logoff is rejected.
The logoff is rejected under the following conditions:
•
The devices are communicating via the protection interface and switching off the device leads to an
interruption in protection-interface communication.
i
i
NOTE
The option used to log the device off is stored in the operational log.
Even if you switch off the device after logoff, the
Device logged off
(_:315) state is stored.
If you want to establish the initial state again after logging off the device, you must log on the device again.
To log on the device, you must use the same option used for logoff. For example, if you have logged off the
device via binary inputs, you must log it on again via the binary inputs. This applies in similar manner if you
have logged off the device via DIGSI or via on-site operation.
Application and Setting Notes
Logoff Options for a Device
You can log off a device as follows:
•
Via the on-site operation panel
•
Via communication via the controllable
Device logoff
(
_:319
)
•
Via the binary inputs, general:
>Device funct.logoff on
(
_:507
) or
>Dev. funct.logoff off
(
_:508
)
Conditions for Logging off the Device
[lo functional logoff device, 1, en_US]
Figure 3-89
Logic for Logging off the Device
The conditions for a successful logoff of the device result from the conditions for every activated protection
function.
3.8.4.2
System Functions
3.8 Other Functions
SIPROTEC 5, High-Voltage Bay Controller, Manual
151
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...