Parameter: Target voltage 2
•
Default setting
(_:14011:157) Target voltage 2
=
110.000 V
With the
Target voltage 2
parameter, you specify the 2nd voltage that the voltage controller is supposed
to reach.
Parameter: Target voltage 3
•
Default setting
(_:14011:158) Target voltage 3
=
110.000 V
With the
Target voltage 3
parameter, you specify the 3rd voltage that the voltage controller is supposed
to reach.
Parameter: Target voltage 4
•
Default setting
(_:14011:159) Target voltage 4
=
110.000 V
With the
Target voltage 4
parameter, you specify the 4th voltage that the voltage controller is supposed
to reach.
Three-Winding Transformer only:
Parameter: Number of target voltage
•
Default setting
(_:15601:164) Number of target voltage
=
1
With this parameter, you specify the number of available
target voltages
(
1 W1/2
to
4 W1/2
). You can
select a target voltage from the available ones using the function key, communication, or binary input.
Note:
Keep in mind that the parameter
Number of target voltage
cannot be influenced by way of the
settings group switching.
You can specify the
target voltages
(
1 W1/2
to
4 W1/2
) in primary, secondary, or in percent.
For the activation of the target voltage 1 to 4 via a binary input, you need a CFC chart.
Parameter: Target voltage 1 w1
•
Default setting
(_:15601:112) Target voltage 1 w1
=
110.000 V
Parameter: Target voltage 1 w2
•
Default setting
(_:15601:146) Target voltage 1 w2
=
110.000 V
Parameter: Target voltage 2 w1
•
Default setting
(_:15601:165) Target voltage 2 w1
=
110.000 V
Parameter: Target voltage 2 w2
•
Default setting
(_:15601:168) Target voltage 2 w2
=
110.000 V
Parameter: Target voltage 3 w1
•
Default setting
(_:15601:166) Target voltage 3 w1
=
110.000 V
Parameter: Target voltage 3 w2
•
Default setting
(_:15601:169) Target voltage 3 w2
=
110.000 V
Parameter: Target voltage 4 w1
•
Default setting
(_:15601:167) Target voltage 4 w1
=
110.000 V
Parameter: Target voltage 4 w2
•
Default setting
(_:15601:170) Target voltage 4 w2
=
110.000 V
Control Functions
6.9 Voltage Controller
SIPROTEC 5, High-Voltage Bay Controller, Manual
491
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...