Addr.
Parameter
C
Setting Options
Default Setting
General
_:5071:1
Synchrocheck 1:Mode
•
off
•
on
•
test
off
_:5071:101
Synchrocheck 1:Min.
operating limit Vmin
0.300 V to 340.000 V
90.000 V
_:5071:102
Synchrocheck 1:Max.
operat. limit Vmax
0.300 V to 340.000 V
110.000 V
_:5071:110
Synchrocheck
1:Max.durat.
sync.process
0.00 s to 3600.00 s; ∞
30.00 s
_:5071:108
Synchrocheck 1:Direct
close command
•
no
•
yes
no
_:5071:126
Synchrocheck 1:Voltage
adjustment
0.500 to 2.000
1.000
General
_:5041:1
Sychr./Asycr.1:Mode
•
off
•
on
•
test
off
_:5041:101
Sychr./Asycr.1:Min. oper-
ating limit Vmin
0.300 V to 340.000 V
90.000 V
_:5041:102
Sychr./Asycr.1:Max.
operat. limit Vmax
0.300 V to 340.000 V
110.000 V
_:5041:110
Sychr./Asycr.
1:Max.durat.
sync.process
0.00 s to 3600.00 s; ∞
30.00 s
_:5041:108
Sychr./Asycr.1:Direct
close command
•
no
•
yes
no
_:5041:126
Sychr./Asycr.1:Voltage
adjustment
0.500 to 2.000
1.000
Dynamic Measuring-Point Switching
Dynamic measuring-point switching provides the capability to connect the voltages used in the Synchro-
check function to various measuring points. In this way, for example, it is possible to use the correct voltage
on the basis of the switch position on the switching devices. If more than 1 measuring point is connected to
V
sync1
or
V sync2
, you must create the
V sync select.
function block in the Circuit-breaker function
group.
Selection of the desired voltage measuring points (
V sync1
and
V sync2
) for the Circuit-breaker function
group is controlled via Continuous Function Chart.
Example
shows an example of a Synchrocheck in a breaker-and-a-half arrangement. If circuit breaker QA2
is to be closed, the reference voltages must be selected from several possible measuring points. This selection
of measuring points is dependent on the switch positions of all circuit breakers and disconnectors.
6.4.5
Control Functions
6.4 Synchronization Function
372
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...