Addr.
Parameter
C
Setting Options
Default Setting
_:1981:101
Definite-T 1:Dropout
delay
0.00 s to 60.00 s
0.00 s
_:1981:6
Definite-T 1:Operate
delay
0.00 s to 60.00 s
1.50 s
Definite-T 2
_:1982:1
Definite-T 2:Mode
•
off
•
on
•
test
off
_:1982:2
Definite-T 2:Operate &
flt.rec. blocked
•
no
•
yes
no
_:1982:3
Definite-T 2:Threshold
5.0 % to 999.9 %
65.0 %
_:1982:4
Definite-T 2:Dropout
ratio
0.40 to 0.99
0.95
_:1982:104
Definite-T 2:Blk. w.
inrush curr. detect.
•
no
•
yes
no
_:1982:101
Definite-T 2:Dropout
delay
0.00 s to 60.00 s
0.00 s
_:1982:6
Definite-T 2:Operate
delay
0.00 s to 60.00 s
0.50 s
Information List
No.
Information
Data Class
(Type)
Type
General
_:2311:301
General:Overcurrent blocking
SPS
O
Group indicat.
_:4501:55
Group indicat.:Pickup
ACD
O
_:4501:57
Group indicat.:Operate
ACT
O
Definite-T 1
_:1981:81
Definite-T 1:>Block stage
SPS
I
_:1981:52
Definite-T 1:Behavior
ENS
O
_:1981:53
Definite-T 1:Health
ENS
O
_:1981:54
Definite-T 1:Inactive
SPS
O
_:1981:56
Definite-T 1:Operate delay expired
ACT
O
_:1981:300
Definite-T 1:Inrush blocks operate
ACT
O
_:1981:55
Definite-T 1:Pickup
ACD
O
_:1981:57
Definite-T 1:Operate
ACT
O
Definite-T 2
_:1982:81
Definite-T 2:>Block stage
SPS
I
_:1982:52
Definite-T 2:Behavior
ENS
O
_:1982:53
Definite-T 2:Health
ENS
O
_:1982:54
Definite-T 2:Inactive
SPS
O
_:1982:56
Definite-T 2:Operate delay expired
ACT
O
_:1982:300
Definite-T 2:Inrush blocks operate
ACT
O
_:1982:55
Definite-T 2:Pickup
ACD
O
_:1982:57
Definite-T 2:Operate
ACT
O
7.25.6
Protection and Automation Functions
7.25 Negative-Sequence Protection
874
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...