Overview of Functions
The Voltage-transformer circuit breaker function detects the tripping of the voltage-transformer circuit
breaker due to short circuits in the voltage-transformer secondary circuits.
The Voltage-transformer circuit breaker function works independently of Measuring-voltage failure detec-
tion and should be used – if possible – in parallel to it.
The tripping of the voltage-transformer circuit breaker has an impact on the quality of the recorded measured-
value data (see chapter
3.3 Processing Quality Attributes
For the following functions the reaction (block/not block) can be set within the function in cases of a tripping
of the voltage-transformer circuit breaker:
•
Overcurrent protection, phases
•
Overcurrent protection, ground
•
Overvoltage protection with 3-phase voltage
•
Overvoltage protection with positive-sequence voltage
•
Overvoltage protection with any voltage
•
Undervoltage protection with 3-phase voltage
•
Undervoltage protection with any voltage
Structure of the Function
shows the position of the function in the device. Every voltage measuring point contains the
Voltage-transformer circuit breaker function.
8.3.3.6
8.3.4
8.3.4.1
8.3.4.2
Supervision Functions
8.3 Supervision of the Secondary System
950
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...