Influencing the Quality by the User
You can influence the processing of data and their quality differently. In DIGSI 5, this is possible at the
following 3 locations:
•
In the Information routing editor for external signals of GOOSE connections
•
In the CFC chart
•
In the Information routing editor for binary input signals of device-internal functions
The following chapters describe in more detail the options regarding this influence as well as the automatic
quality processing.
If a GOOSE connection is the data source of a binary input signal of a device-internal function, you can influ-
ence processing of the quality at 2 locations: at the GOOSE connection and at the input signal of the function.
This is based on the following: A GOOSE date can be distributed within the receiving device to several func-
tions. The GOOSE connection setting (influence) affects all functions. However, if different functions require
customized settings, these are then set directly at the binary input signal of the function.
Quality Processing/Affected by the User for Received GOOSE Values
The properties of quality processing have changed with the introduction of GOOSE Later Binding. You can find
information about the former quality processing in chapter
Previous Quality Processing/Affected by the User
for Received GOOSE Values, Page 81
.
In the Information Routing Editor, you can influence the data value and quality of all data types. The
following figure shows the possible influence using the example of a DPC data type. All setting options are
effective for the device receiving the data.
•
In the DIGSI 5 project tree, double-click Information Routing.
•
Select either the desired signal in the External Signals group or the signal of a function activated via the
GOOSE column.
•
Open the Properties window and select the Processing Quality Attributes sheet.
3.3.2
System Functions
3.3 Processing Quality Attributes
SIPROTEC 5, High-Voltage Bay Controller, Manual
77
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...