GETTING STARTED GUIDE

IC-3173

Industrial Controller with Reconfigurable I/O

The IC-3173 is a high-performance, fanless embedded system designed for rugged industrial
applications. This document explains how to install and configure the IC-3173.

Contents

Safety Information.................................................................................................................... 1
Electromagnetic Compatibility Guidelines...............................................................................2
Preparing the Environment....................................................................................................... 3
Configuring the Hardware........................................................................................................ 3

Connecting the System Power Supply.............................................................................. 4
Connecting the Isolated Outputs Power Supply............................................................... 5

Configuring the IC-3173 for NI Linux Real-Time....................................................................6

Required Components.......................................................................................................7
Connecting to the Development Computer.......................................................................8
Using Vision Builder AI with the IC-3173....................................................................... 8
Installing the NI Industrial Controller Device Drivers..................................................... 8

Setting a System Password..................................................................................................... 10
Troubleshooting...................................................................................................................... 10
Worldwide Support and Services............................................................................................ 13

Safety Information

Caution

 

The following paragraphs contain important safety information you must

follow when installing and operating the device.

Do not operate the device in a manner not specified in the documentation. Misuse of the
device may result in a hazard and may compromise the safety protection built into the device.
If the device is damaged, turn it off and do not use it until service-trained personnel can check
its safety. If necessary, return the device to National Instruments for repair.

Keep away from live circuits. Do not remove equipment covers or shields unless you are
trained to do so. If signal wires are connected to the device, hazardous voltages can exist even
when the equipment is turned off. To avoid a shock hazard, do not perform procedures
involving cover or shield removal unless you are qualified to do so. Disconnect all field power
prior to removing covers or shields.

Because of the danger of introducing additional hazards, do not install unauthorized parts or
modify the device. Use the device only with the chassis, modules, accessories, and cables

Summary of Contents for IC-3173

Page 1: ...ortant safety information you must follow when installing and operating the device Do not operate the device in a manner not specified in the documentation Misuse of the device may result in a hazard...

Page 2: ...imum voltage for which the device is rated Do not exceed the maximum ratings for the device Remove power from signal lines before connection to or disconnection from the device Electromagnetic Compati...

Page 3: ...tion To ensure the specified EMC performance product installation requires either special considerations or user installed add on devices See the product installation instructions for further informat...

Page 4: ...r Accessible Battery Compartment not pictured 12 RS 232 RS 485 Serial Port 13 USB 3 0 Ports 14 Primary Gigabit Ethernet Port 15 Retention Mounts for USB 3 0 Ports 16 Retention Mounts for USB 2 0 Ports...

Page 5: ...tion The C terminals are internally connected to each other 6 Install the power connector into SYS PWR IN on the front panel of the controller and tighten the connector screw flanges to 0 3 to 0 4 N m...

Page 6: ...f the power connector plug and tighten the terminal screw to 0 2 to 0 25 N m 1 8 to 2 2 lb in of torque 5 Connect the negative lead of the isolated outputs power source to the C terminal of the power...

Page 7: ...male to pigtail cable part number 156083 03 for 3 meter cable 44 pin D SUB male to 44 position D SUB female cable part number 156084 03 for 3 meter cable or part number 156084 0R5 for 0 5 meter cable...

Page 8: ...r network device on the same network as the development computer 4 Verify the ACTIVITY LINK LED on the port is on or blinking The device negotiates an IP address when connected to a network with a DHC...

Page 9: ...tware set a Expand the IC 3173 under Remote Systems b Click the Software item below the IC 3173 in the configuration tree c Click Add Remove Software on the NI MAX toolbar to launch the LabVIEW Real T...

Page 10: ...words If you forget the password you must contact NI and reformat the controller Troubleshooting The IC 3173 Does Not Appear in MAX The IC 3173 may not be powered Verify that there is system power to...

Page 11: ...f you are having difficulty detecting the system and setting up the IC 3173 on your network you must configure the firewall to open the TCP UDP ports used by the IC 3173 and the host machine Refer to...

Page 12: ...ontroller either booted into an unsupported operating system was interrupted during the boot process or detected an unrecoverable software error Continuous blink red This indicates a hardware error An...

Page 13: ...declaration of conformity This system affords the user protection for electromagnetic compatibility EMC and product safety You can obtain the DoC for your product by visiting ni com certification If...