Channel
=
Setting Notes for the Protection Device in Feeder 2
The Arc protection function operates with 3 stages.
Stage 1 and 2 (supervision of busbar compartment and circuit-breaker compartment):
Set the parameters of the stages as follows:
•
Parameter:
Operating mode
=
light only
•
Parameter:
Sensor
=
point sensor
•
Parameter:
External trip initiation
=
no
•
Parameter:
Operate & flt.rec. blocked
=
yes
•
Parameter:
Channel
= (Stage 1) → busbar-compartment supervision in feeder 2
Parameter:
Channel
= (Stage 2) → circuit-breaker compartment supervision in feeder 2
Stage 3 (supervision of cable-connection compartment):
Set the parameters of the stage as follows:
•
Parameter:
Operating mode
=
current and light
•
Parameter:
Sensor
=
point sensor
•
Parameter:
External trip initiation
=
current
The protection device in the infeed evaluates the current. If the measured current exceeds the threshold
values
Threshold I>
and/or
Threshold 3I0>
, the protection device in the infeed returns the indica-
tion
Current detected
to the protection device in the feeder.
Only if the indication in the feeder device
Current detected
is connected with the signal
>External
current
an external trip initiation for this stage is effective.
•
Parameter:
Operate & flt.rec. blocked
=
no
•
Parameter:
Channel
=
Setting Notes for the Protection Device in the Infeed
The Arc protection function operates with 7 stages.
Stage 1 (busbar-compartment supervision):
•
Parameter:
Operate & flt.rec. blocked
=
no
If an arc is detected in the busbar compartment of the infeed and the thresholds
Threshold I>
and/or
Threshold 3I0>
are exceeded, an operate indication is generated immediately.
•
Parameter:
Channel
=
•
Parameter:
Operating mode
=
current and light
•
Parameter:
Sensor
=
point sensor
•
Parameter:
External trip initiation
=
no
Stage 2 (circuit-breaker compartment supervision):
•
Parameter:
Operate & flt.rec. blocked
=
yes
If an arc is detected in the circuit-breaker compartment of the infeed (light-gray point sensors in
), a pickup indication is generated immediately. The arc is switched off by a superordinate
protection device.
•
Parameter:
Channel
=
•
Parameter:
Operating mode
=
current and light
Protection and Automation Functions
7.29 Arc Protection
SIPROTEC 5, High-Voltage Bay Controller, Manual
927
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...