Operate Curve
If the function picks up, the logarithmic inverse-time characteristic curve is processed. A time value T
op
is
calculated for every input value exceeding 95 % of the threshold value. An integrator accumulates the value
1/T
op
. If the accumulated integral reaches the fixed value 1, the stage operates.
The curve used to calculate the time value T
op
is shown in the following graphic. The curve is composed of 2
sections with different slops. 7 parameters are used to define the logarithmic inverse time with knee-point
characteristic curve. The parameter
Max. time of the curve
determines the initial time value of the
characteristic curve, and relates to the 3I0
Threshold
value. The transition point is defined by parameter
Knee-point current
and parameter
Knee-point time
. The parameter
Min. time of the curve
indicates the lower time limit, and parameter
Current at Min. time
determines the current value at
Min. time of the curve
. The parameter
Time dial
servers as a time factor to the operate time.
[dwloinkn-300913, 3, en_US]
Figure 7-118
Operate Curve of the Logarithmic Inverse Time with Knee-Point Characteristic (In the Example
of
Threshold
=
0.004 A
)
Application and Setting Notes
Apart from the operate curve, this type of stage is almost identical to the Inverse-time overcurrent protec-
tion – advanced stage (see chapter
). The only difference is that the dynamic settings
change functionality is not available.
This section only discusses the nature of the operate curve. For further functionality, refer to chapter
7.7.6.2 Application and Setting Notes
Parameter:
Threshold
•
Default setting
(_:3) Threshold
=
1.20 A
You can use the
Threshold
parameter to define the pickup value of the stage corresponding to the specific
application.
7.7.8.2
Protection and Automation Functions
7.7 Directional Overcurrent Protection, Ground
SIPROTEC 5, High-Voltage Bay Controller, Manual
737
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...