Parameter Value
Description
via control
The switchover between the settings groups can only be initiated via a
communication connection from a substation automation technology or via
a CFC chart.
The communication protocols IEC 60870-5-103, IEC 60870-5-104, IEC
61850, DNP or Modbus TCP can be used for switching the settings groups
via a communication connection.
via binary input
The switchover between the settings groups functions exclusively via the
binary input signals routed to the settings group switching.
settings group 1
...
settings group 8
They define the active settings groups. You can define the active settings
groups in DIGSI 5, or directly on the device via the on-site operation.
Settings
Addr.
Parameter
C
Setting Options
Default Setting
Change group
_:113
General:Number settings
groups
1 to 8
1
_:114
General:Activat. of
settings group
•
via control
•
via binary input
•
settings group 1
•
settings group 2
•
settings group 3
•
settings group 4
•
settings group 5
•
settings group 6
•
settings group 7
•
settings group 8
settings group 1
Information List
No.
Information
Data Class
(Type)
Type
General
_:500
General:>SG choice bit 1
SPS
I
_:501
General:>SG choice bit 2
SPS
I
_:502
General:>SG choice bit 3
SPS
I
_:300
General:Act. settings group 1
SPC
C
_:301
General:Act. settings group 2
SPC
C
_:302
General:Act. settings group 3
SPC
C
_:303
General:Act. settings group 4
SPC
C
_:304
General:Act. settings group 5
SPC
C
_:305
General:Act. settings group 6
SPC
C
_:306
General:Act. settings group 7
SPC
C
_:307
General:Act. settings group 8
SPC
C
General Device Settings
Overview
In Device settings in DIGSI 5, you find the following general settings.
3.10.1.5
3.10.1.6
3.10.2
3.10.2.1
System Functions
3.10 Device Settings
164
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...