Addr.
Parameter
C
Setting Options
Default Setting
Dyn.set: bin.input
_:752:34
Definite-T 2:Effected by
binary input
•
no
•
yes
no
_:752:41
Definite-T 2:Stage
blocked
•
no
•
yes
no
_:752:19
Definite-T 2:Threshold
1 A @ 100 Irated 0.010 A to 35.000 A
1.200 A
5 A @ 100 Irated 0.05 A to 175.00 A
6.00 A
1 A @ 50 Irated
0.010 A to 35.000 A
1.200 A
5 A @ 50 Irated
0.05 A to 175.00 A
6.00 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
1.200 A
5 A @ 1.6 Irated
0.002 A to 8.000 A
6.000 A
_:752:25
Definite-T 2:Operate
delay
0.00 s to 60.00 s
0.30 s
Information List
No.
Information
Data Class
(Type)
Type
General
_:2311:500
General:>Activation emg. mode
SPS
I
_:2311:300
General:Emergency mode act.
SPS
O
Group indicat.
_:4501:55
Group indicat.:Pickup
ACD
O
_:4501:57
Group indicat.:Operate
ACT
O
Definite-T 1
_:751:81
Definite-T 1:>Block stage
SPS
I
_:751:84
Definite-T 1:>Activ. dyn. settings
SPS
I
_:751:500
Definite-T 1:>Block delay & op.
SPS
I
_:751:54
Definite-T 1:Inactive
SPS
O
_:751:52
Definite-T 1:Behavior
ENS
O
_:751:53
Definite-T 1:Health
ENS
O
_:751:60
Definite-T 1:Inrush blocks operate
ACT
O
_:751:62
Definite-T 1:Dyn.set. AR cycle1act.
SPS
O
_:751:63
Definite-T 1:Dyn.set. AR cycle2act.
SPS
O
_:751:64
Definite-T 1:Dyn.set. AR cycle3act.
SPS
O
_:751:65
Definite-T 1:Dyn.set. ARcycl.>3act
SPS
O
_:751:66
Definite-T 1:Dyn.set. CLP active
SPS
O
_:751:67
Definite-T 1:Dyn.set. BI active
SPS
O
_:751:68
Definite-T 1:Dyn. set. blks. pickup
SPS
O
_:751:55
Definite-T 1:Pickup
ACD
O
_:751:56
Definite-T 1:Operate delay expired
ACT
O
_:751:57
Definite-T 1:Operate
ACT
O
7.5.4.4
Protection and Automation Functions
7.5 Overcurrent Protection, Ground
SIPROTEC 5, High-Voltage Bay Controller, Manual
647
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...