Figure 9-39
Settings for Example 2
Each measuring transducer makes available the scaled measured value in the information matrix (these are
the temperature values in the examples) and the original current measured value in mA for further processing.
The measuring-transducer values can be displayed in the display image and processed with CFC charts.
Application and Setting Notes
Parameter: Unit
•
Recommended setting value
(_:103) Unit
=
°C
You use the setting
Unit
to specify which physical unit of measurement the measured values represent. The
possible setting values are listed in the settings table.
Parameter: Conversion factor
The
(_:104) Conversion factor
setting allows you to set the conversion factor for the measuring trans-
ducer.
Parameter: Resolution
•
Default setting
(_:108) Resolution
=
0.1
The
Resolution
setting is used to specify the measured value resolution.
Parameter: Range active
•
Default setting
(_:107) Range active
=
false
If you do not activate the
Range active
setting (no x in the check box), the function operates over the
range -24 mA to +24 mA. The setting of the range for the scaled value goes from a usable range of -20 mA to
+20 mA.
If you activate the
Range active
setting, then 4 additional settings
Upper limit
,
Upper limit -
Sensor
,
Lower limit
and
Lower limit - Sensor
appear.
Parameter: Upper limit, Lower limit, Upper limit - Sensor and Lower limit - Sensor
•
Default setting
(_:105) Upper limit
=
20000 mA
•
Default setting
(_:109) Upper limit - Sensor
=
100
•
Default setting
(_:106) Lower limit
=
4000 mA
•
Default setting
(_:110) Lower limit - Sensor
=
100
If you activate the
Range active
setting, then 4 additional settings
Upper limit
,
Lower limit
,
Upper
limit - Sensor
, and
Lower limit - Sensor
appear. The setting
Upper limit - Sensor
is the
9.12.4
Measured Values, Energy Values, and Supervision of the Primary System
9.12 Measuring Transducers
SIPROTEC 5, High-Voltage Bay Controller, Manual
1053
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...