Overcurrent Protection, Phases
Overview of Functions
The Overcurrent protection, phases function (ANSI 50/51):
•
Detects short circuits in electrical equipment
•
Can be used as backup overcurrent protection in addition to the main protection
Structure of the Function
The Overcurrent protection, phases function is used in protection function groups. 2 kinds of functions are
available for the 3-phase overcurrent protection:
•
Overcurrent protection, phases – advanced (50/51 OC-3ph-A)
•
Overcurrent protection, phases – basic (50/51 OC-3ph-B)
Only the Advanced function type is available in the bay controllers. The Basic function type is provided for
standard applications. The Advanced function type offers more functionality and is provided for more complex
applications.
Both function types are preconfigured by the manufacturer with 2 Definite-time overcurrent protection
stages and with 1 Inverse-time overcurrent protection stage.
In the Overcurrent protection, phase – advanced function type, the following stages can be operated simul-
taneously:
•
Maximum of 4 stages Definite-time overcurrent protection – advanced
•
1 stage Inverse-time overcurrent protection – advanced
•
1 stage User-defined overcurrent protection characteristic curve
In the Overcurrent protection, phases – basic function type, the following stages can be operated simulta-
neously:
•
Maximum of 4 stages Definite-time overcurrent protection – basic
•
1 stage Inverse-time overcurrent protection – basic
Stages that are not preconfigured are shown in gray in the following figures. Apart from the tripping delay
characteristic, the stages are identical in structure.
The optional function block Filter offered in the advanced function allows to gain harmonics or to compensate
the amplitude attenuation for the RMS value.
The group-indication output logic generates the following group indications of the protection function by the
logical OR of the stage-selective indications:
•
Pickup
•
Operate
7.4
7.4.1
7.4.2
Protection and Automation Functions
7.4 Overcurrent Protection, Phases
598
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...