i
i
NOTE
In case of power-system incidents, especially in case of transmission incidents and influence of voltage-
stabilizing measures via power-electronic components (reactive-power compensation through SVC), the
magnitude and the phase angle of the voltage can change. Sensitive settings can lead to overfunction.
Therefore, it is reasonable to block the Rate of Frequency Change Protection if other protection func-
tions, for example, residual voltage or negative-sequence voltage, pick up. To do this, use the blocking
input
>Block stage
and connect it via CFC.
Settings
Addr.
Parameter
C
Setting Options
Default Setting
General
_:13171:101
General:Minimum
voltage
3.000 V to 175.000 V
37.500 V
_:13171:137
General:Measuring
window
2 periods to 5 periods
5 periods
df/dt falling1
_:13231:1
df/dt falling1:Mode
•
off
•
on
•
test
off
_:13231:2
df/dt falling1:Operate &
flt.rec. blocked
•
no
•
yes
no
_:13231:3
df/dt falling1:Threshold
0.100 Hz/s to 20.000 Hz/s
3.000 Hz/s
_:13231:4
df/dt falling1:Dropout
differential
0.02 Hz/s to 0.99 Hz/s
0.10 Hz/s
_:13231:6
df/dt falling1:Operate
delay
0.00 s to 60.00 s
1.00 s
df/dt rising1
_:13201:1
df/dt rising1:Mode
•
off
•
on
•
test
off
_:13201:2
df/dt rising1:Operate &
flt.rec. blocked
•
no
•
yes
no
_:13201:3
df/dt rising1:Threshold
0.100 Hz/s to 20.000 Hz/s
3.000 Hz/s
_:13201:4
df/dt rising1:Dropout
differential
0.02 Hz/s to 0.99 Hz/s
0.10 Hz/s
_:13201:6
df/dt rising1:Operate
delay
0.00 s to 60.00 s
1.00 s
Information List
No.
Information
Data Class
(Type)
Type
General
_:13171:300
General:Undervoltage blocking
SPS
O
_:13171:301
General:df/dt
MV
O
Group indicat.
_:4501:55
Group indicat.:Pickup
ACD
O
_:4501:57
Group indicat.:Operate
ACT
O
df/dt falling1
_:13231:81
df/dt falling1:>Block stage
SPS
I
_:13231:54
df/dt falling1:Inactive
SPS
O
7.21.4.3
7.21.4.4
Protection and Automation Functions
7.21 Rate of Frequency Change Protection
850
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...