Synchronization Function
Operating Modes
Synchrocheck
Switching synchronous systems
Switching asynchronous systems
Switching synchronous/asynchronous systems with balancing commands
De-energized switching
Direct closing command
Balancing Voltage
Balancing Frequency
Setting Values
Supervision/Delay/Pulse times:
Max.durat. sync.process
0.00 s to 3 600.00 s or ∞ (ineffec-
tive)
Increments of 0.01 s
Supervision time de-energized
switching
0.00 s to 60.00 s
Increments of 0.01 s
Closure delay
0.00 s to 60.00 s
Increments of 0.01 s
T V pulse min/T f pulse min
0.01 s to 1.00 s
Increments of 0.01 s
T V pulse max/T f pulse max
0.01 s to 60.00 s
Increments of 0.01 s
T pause V/T pause f
0.01 s to 60.00 s
Increments of 0.01 s
T close without balancing
1.00 s to 100.00 s
Increments of 0.01 s
Voltage threshold values:
Upper voltage limit V
max
0.300 V to 340.000 V (phase-to-
phase)
Increments of 0.001 V
Lower voltage limit V
min
0.300 V to 340.000 V (phase-to-
phase)
Increments of 0.001 V
V<, for off-circuit conditions
V>, for voltage present
0.300 V to 170.000 V (phase-to-
phase)
0.300 V to 340.000 V (phase-to-
phase)
Increments of 0.001 V
Increments of 0.001 V
Differential values, changeover thresholds asynchronous/synchronous/balancing:
Voltage differences
V2 > V1; V2 < V1
0.000 V to 170.000 V
Increments of 0.001 V
Frequency difference f2 > f1;
f2 < f1
0.000 Hz to 2.000 Hz (synchro-
nous)
0.000 Hz to 4.000 Hz (asynchro-
nous)
Increments of 0.001 Hz
Angle difference α2 > α1; α2 < α1
0
o
to 90
o
Increments of 1
o
Δf threshold ASYN <-> SYN
0.010 Hz to 0.200 Hz
Increments of 0.001 Hz
Δf set point for balancing
-1.00 Hz to 1.00 Hz
Increments of 0.01 Hz
Δf for the kick pulse
-1.00 Hz to 1.00 Hz
Increments of 0.01 Hz
Adjustments of the sides:
Angle adjustment
0.0
o
to 360.0
o
Increments of 0.1
o
Voltage adjustment
0.500 to 2.000
Increments of 0.001
Circuit breaker
Closing time of the circuit breaker
0.01 s to 0.60 s
Increments of 0.01 s
11.34
Technical Data
11.34 Synchronization Function
SIPROTEC 5, High-Voltage Bay Controller, Manual
1177
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...