When determining the setting value, please keep in mind the measurement method and the measuring
connection that you have selected. If you work with the positive-sequence voltage, remember that the
maximum voltage is equal to the phase-to-ground voltage. The default setting is referred to this value.
Parameter: Dropout differential
•
Recommended setting value
(_:2311:109) Dropout differential
=
20 mHz
Due to the high-precision frequency measurement, the recommended setting value for the
Dropout
differential
can remain at 20 mHz. For a later dropout of the stage, increase the setting value of the
dropout differential. For example, if the pickup value (parameter
Threshold
) of the stage is set to 51.5 Hz
and the
Dropout differential
to 100 mHz, the stage will drop out at 51.4 Hz.
Setting example of the overfrequency protection for generators
If the overspeed limiter does not function properly, the overfrequency protection issues an additional alarm
indication. Overspeeding can be caused by load shedding or by a disturbance of the speed limiter (for
example, in an island network).
One possible frequency limit could be 1.03 f
rated
. If the machine does not recover, it can be shut down with a
2nd stage of, for example, 1.08 f
rated
. To avoid overfunctions, you can set a sufficient time delay for the
warning indication or tripping.
For this application, 2 stages of the overfrequency protection are used. The following table shows a setting
suggestion.
Stage
Caused by
Setting Values
At f
rated
= 50 Hz
At f
rated
= 60 Hz
Delay
f1>
Warning or disconnection
51.50 Hz
61.80 Hz
20.00
f2>
Shutdown
54.00 Hz
64.80 Hz
5.00
i
i
NOTE
This table shows one example of a possible frequency protection setting. The setting values can differ
depending on the application.
Settings
Addr.
Parameter
C
Setting Options
Default Setting
General
_:2311:101
General:Minimum voltage
3.000 V to 175.000 V
37.500 V
_:2311:109
General:Dropout differen-
tial
20 mHz to 2000 mHz
20 mHz
Stage 1
_:31:1
Stage 1:Mode
•
off
•
on
•
test
off
_:31:2
Stage 1:Operate & flt.rec.
blocked
•
no
•
yes
no
_:31:3
Stage 1:Threshold
40.00 Hz to 70.00 Hz
1.00 Hz
_:31:6
Stage 1:Operate delay
0.00 s to 600.00 s
10.00 s
Stage 2
_:32:1
Stage 2:Mode
•
off
•
on
•
test
off
_:32:2
Stage 2:Operate & flt.rec.
blocked
•
no
•
yes
no
7.18.5
Protection and Automation Functions
7.18 Overfrequency Protection
SIPROTEC 5, High-Voltage Bay Controller, Manual
827
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...