Thermal Overload Protection, 3-Phase – Advanced
Setting Value for the Function Block Filter
h(0)
-100.000 to 100.000
Increments of 0.001
h(1)
-100.000 to 100.000
Increments of 0.001
h(2)
-100.000 to 100.000
Increments of 0.001
h(3)
-100.000 to 100.000
Increments of 0.001
h(4)
-100.000 to 100.000
Increments of 0.001
Setting Values/Increments for the Protection Stage
Threshold current
warning
1 A @ 50 and 100 Irated
0.030 A to 35.000 A
Increments of 0.001 A
5 A @ 50 and 100 Irated
0.15 A to 175.00 A
Increments of 0.01 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
Increments of 0.001 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
Increments of 0.001 A
Threshold thermal warn.
50 % to 100 %
Increments of 1 %
Dropout threshold operate
50 % to 99 %
Increments of 1 %
Emerg. start T overtravel
0 s to 15 000 s
Increments of 10 s
K-factor acc. to IEC 60225-8
0.10 to 4.00
Increments of 0.01
Thermal time constant
10 s to 60 000 s
Increments of 1 s
Cooling time constant
10 s to 60 000 s
Increments of 1 s
Imax thermal
1 A @ 50 and 100 Irated
0.030 A to 10.000 A
Increments of 0.001 A
5 A @ 50 and 100 Irated
0.15 A to 50.00 A
Increments of 0.01 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
Increments of 0.001 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
Increments of 0.001 A
Imin cooling
1 A @ 50 and 100 Irated
0.000 A to 10.000 A
Increments of 0.001 A
5 A @ 50 and 100 Irated
0.00 A to 50.00 A
Increments of 0.01 A
1 A @ 1.6 Irated
0.000 A to 1.600 A
Increments of 0.001 A
5 A @ 1.6 Irated
0.000 A to 8.000 A
Increments of 0.001 A
Temperature rise at Irated
40 K to 200 K
Increments of 1 K
Default temperature
-55°C to 55°C
Increments of 1°C
Minimal temperature
-55°C to 40°C
Increments of 1°C
Dropout Ratios
Tripping threshold (fixed at 100 %)
Dropout if value drops below operate indication
dropout threshold
Thermal warning threshold
About 0.99 of the setting value
Current warning threshold
About 0.95 of the setting value
Frequency Range of the Input Signals
The function captures input signals up to the 50th harmonic.
11.31
Technical Data
11.31 Thermal Overload Protection, 3-Phase – Advanced
1172
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...