Application and Setting Notes
Parameter:
Level of warning 1
•
Default setting
(_:101) Level of warning 1
=
5 %
With the parameter
Level of warning 1
, you define the percentage the measured value is allowed to
exceed the parameter
CB make time
at the output
Make time
, before the output
Warning 1
is set. The
output
Warning 1
then drops out after 100 ms.
Parameter:
Level of warning 2
•
Default setting
(_:102) Level of warning 2
=
10 %
With the parameter
Level of warning 2
, you define the percentage the measured value is allowed to
exceed the parameter
CB make time
at the output
Make time
, before the output
Warning 2
is set. The
output
Warning 2
then drops out after 100 ms.
Parameter:
Oper.current threshold
•
Default setting
(_:103) Oper.current threshold
=
0.100 A
With the parameter
Oper.current threshold
, you define the current threshold. If the measured value
exceeds this threshold, the measured value is detected as flowing operating current. As soon as an operating
current flows, the end of the time interval
Make time
is detected.
Parameter:
Delay correction time
•
Default setting
(_:104) Delay correction time
=
0.000 s
With the parameter
Delay correction time
, you define a correction value which will be subtracted from
the
Make time
during calculation. This allows you to compensate delays caused by the system, for example,
relay residual times, if necessary.
Settings
Addr.
Parameter
C
Setting Options
Default Setting
Supv.CB mak.t.
_:1
Supv.CB mak.t.:Mode
•
off
•
on
•
test
off
_:101
Supv.CB mak.t.:Level of
warning 1
1 % to 100 %
5 %
_:102
Supv.CB mak.t.:Level of
warning 2
1 % to 100 %
10 %
_:103
Supv.CB
mak.t.:Oper.current
threshold
1 A @ 100 Irated 0.030 A to 35.000 A
0.100 A
5 A @ 100 Irated 0.15 A to 175.00 A
0.50 A
1 A @ 50 Irated
0.030 A to 35.000 A
0.100 A
5 A @ 50 Irated
0.15 A to 175.00 A
0.50 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
0.100 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
0.500 A
_:104
Supv.CB mak.t.:Delay
correction time
-0.050 s to 0.050 s
0.000 s
9.6.7.2
9.6.7.3
Measured Values, Energy Values, and Supervision of the Primary System
9.6 Circuit-Breaker Wear Monitoring
SIPROTEC 5, High-Voltage Bay Controller, Manual
1035
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...