Signal
Description
Routing Options
Close command
This signal executes all closing operations.
The
Output time
parameter affects the signal.
The signal is pending for the duration of this period, with
the following exception: The signal is canceled before
expiration of the period if the auxiliary contacts report
that the circuit breaker is closed before expiration of the
period.
Closing operations are always 3-pole operations.
Normal routing
Command active
This signal is active as long as one of the binary outputs
assigned to the signals
Trip/open cmd. 3-pole
and
Close command
is active because a switching command
is being executed by the control.
Normal routing
Acquisition of Circuit-Breaker Auxiliary Contacts and Further Information
To determine the circuit-breaker switch position, the Circuit-breaker function block provides position signals
(see next figure).
These signals are of the Double-point indication (DPC) type. A double-point indication can be routed to
2 binary inputs so that the open and closed circuit-breaker switch positions can be reliably acquired.
[loerfass-091210-01.tif, 1, en_US]
Figure 5-39
Acquisition of the Circuit-Breaker Information
Signal
Type
Description
Position 3-pole
DPC
Acquisition of the 3-pole circuit-breaker switch position.
The position 3-pole circuit breaker open and/or the position 3-pole
circuit breaker closed can be acquired by routing to 1 or 2 binary
inputs.
5.6.5.3
Function-Group Types
5.6 Function-Group Type Circuit Breaker, 1-/3-Pole
238
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...