The phase sequence of the system is set in the device via the
Phase sequence
parameter for generator
operation. The
Inverted phases
parameter is used to set which phase is swapped for the relevant meas-
uring point. The swap is communicated to the measuring point via the binary input signal
>Invert Phases
.
The changed phase sequence is then included for calculation of the measurands at the measuring point.
In accordance with
the phase sequence is set to
ABC
. A is swapped with C in motor operation.
The
Inverted phases
parameter must be set to
AC
for the measuring points of current measured values 2
and current measured values 3. As a result, the phase assignment for the differential protection IED2 and the
impedance protection IED3 is correct. The positive-sequence and negative-sequence current is calculated
correctly.
The following logic diagram shows the principle for determining the present phase assignment and measured
variables with the example of currents.
The switchover of the phase sequence is only authorized for a time at which no measured values are pending
at the selected measuring points. The switchover command must be present for at least 200 ms. The change
of phase sequence is only implemented if the measurands at the measuring points that are to be switched are
under 5 % of the rated variables. If the currents of the measuring points of current measured values 2 and
current measured values 3 of the example fall below 5 % of their rated variables, the switchover is released
and the set phases are switched with active binary input.
[lophrgph-190517-01.vsd, 1, en_US]
Figure 7-180
Measured Values for Changed-Over Phases
Application and Setting Notes
Parameter: Phase sequence
•
Default setting
(_:101) Phase sequence
=
ABC
ABC
Phase sequence A, B, C
ACB
Phase sequence A, B, C
Parameter: Inverted phases
•
Default setting
(_:106) Inverted phases
=
none
none
No phase exchange
AC
Phase A changed over with phase C
BC
Phase B changed over with phase C
7.23.4
Protection and Automation Functions
7.23 Phase-Sequence Switchover
SIPROTEC 5, High-Voltage Bay Controller, Manual
865
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...