Settings
Addr.
Parameter
C
Setting Options
Default Setting
Definite-T 1
_:12661:1
Definite-T 1:Mode
•
off
•
on
•
test
off
_:12661:2
Definite-T 1:Operate &
flt.rec. blocked
•
no
•
yes
no
_:12661:27
Definite-T 1:Blk. w.
inrush curr. detect.
•
no
•
yes
no
_:12661:8
Definite-T 1:Method of
measurement
•
fundamental comp.
•
RMS value
fundamental
comp.
_:12661:3
Definite-T 1:Threshold
1 A @ 100 Irated 0.030 A to 35.000 A
1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A
6.00 A
1 A @ 50 Irated
0.030 A to 35.000 A
1.200 A
5 A @ 50 Irated
0.15 A to 175.00 A
6.00 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
1.200 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
6.000 A
_:12661:6
Definite-T 1:Operate
delay
0.00 s to 60.00 s
0.30 s
Definite-T 2
_:12662:1
Definite-T 2:Mode
•
off
•
on
•
test
off
_:12662:2
Definite-T 2:Operate &
flt.rec. blocked
•
no
•
yes
no
_:12662:27
Definite-T 2:Blk. w.
inrush curr. detect.
•
no
•
yes
no
_:12662:8
Definite-T 2:Method of
measurement
•
fundamental comp.
•
RMS value
fundamental
comp.
_:12662:3
Definite-T 2:Threshold
1 A @ 100 Irated 0.030 A to 35.000 A
1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A
6.00 A
1 A @ 50 Irated
0.030 A to 35.000 A
1.200 A
5 A @ 50 Irated
0.15 A to 175.00 A
6.00 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
1.200 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
6.000 A
_:12662:6
Definite-T 2:Operate
delay
0.00 s to 60.00 s
0.10 s
Information List
No.
Information
Data Class
(Type)
Type
Group indicat.
_:4501:55
Group indicat.:Pickup
ACD
O
_:4501:57
Group indicat.:Operate
ACT
O
Definite-T 1
_:12661:81
Definite-T 1:>Block stage
SPS
I
_:12661:500
Definite-T 1:>Block delay & op.
SPS
I
_:12661:54
Definite-T 1:Inactive
SPS
O
_:12661:52
Definite-T 1:Behavior
ENS
O
7.8.3.3
7.8.3.4
Protection and Automation Functions
7.8 Overcurrent Protection, 1-Phase
750
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...