Dropout Ratio
Min./max. operating limit:
1 % of the setting value
Voltage differential
10 % of the setting value or 0.5 V
De-energized/energized
5 % of the setting value
Frequency difference
3 mHz
Angle difference
0.1
o
Measured Values of the Synchronization Function
Reference voltage V1
•
Range
•
Tolerance at rated frequency
In kV primary, in V secondary or in % V
rated
Display always as phase-to-phase voltage
10 % to 120 % of V
rated
≤ 1% of the measured value or 0.5% V
rated
Voltage to be synchronized V2
•
Range
•
Tolerance at rated frequency
In kV primary, in V secondary or in % V
rated
Display always as phase-to-phase voltage
10 % to 120 % of V
rated
≤ 1% of the measured value or 0.5% V
rated
Frequency of the voltage V1f1
•
Range
•
Tolerance at rated frequency
f1 in Hz
25 Hz ≤ f ≤ 70 Hz
1 mHz
Frequency of the voltage V1f2
•
Range
•
Tolerance at rated frequency
f2 in Hz
25 Hz ≤ f ≤ 70 Hz
1 mHz
Voltage difference V2-V1
•
Range
•
Tolerance at rated frequency
In kV primary, in V secondary or in % V
rated
Display always as phase-to-phase voltage in relation
to side 1
10 % to 120 % of V
rated
≤ 1% of the measured value or 0.5% V
rated
Frequency difference f2-f1
•
Range
•
Tolerance at rated frequency
In mHz
f
rated
± 10 %
1 mHz
Angle difference λ2-λ1
•
Range
•
Tolerance at rated frequency
In
o
-180
o
to +180
o
0.5
o
Times
Measuring time, after switching on the variables
Approx. 80 ms
Operating Range
Voltage
20 V to 340 V
Frequency
f
rated
-4 Hz ≤ f
rated
≤ f
rated
+4 Hz
Tolerances
Tolerances of the voltage settings
2 % of the pickup value or 1 V
Voltage difference V2>V1; V2<V1
1 V
Frequency difference f2>f1; f2<f1
10 mHz
Angle difference α2>α1; α2<α1
1
o
Technical Data
11.34 Synchronization Function
1178
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...