Fundamental and Symmetrical Components
The fundamental components are calculated from the frequency-tracked instantaneous values through a
Fourier filter (integration interval: one period). The results are phasor values that are described by way of the
amount and phase angle.
In accordance with the transformation matrix, the symmetrical components are calculated from the voltage
and current phasors. These are also phasor quantities.
Fundamental Components
Table 9-2
Fundamental Components
Values
Primary
Secon-
dary
Phase
Angle
% Referenced to
V
A
, V
B
, V
C
Phase-to-ground voltage
kV
V
°
Rated operating voltage of primary
values/√3
V
N
Measured neutral-point displace-
ment voltage
kV
V
°
Rated operating voltage of primary
values/√3
V
12
, V
23
,
V
31
Phase-to-phase voltage
kV
V
°
Rated operating voltage of the
primary values
I
A
, I
B
, I
C
Phase currents
A
A
°
Rated operating current of the
primary values
I
N
Neutral-point phase current
A
A
°
Rated operating current of the
primary values
Symmetrical Components
Table 9-3
Symmetrical Components
Values
Primary
Secon-
dary
Phase
Angle
% Referenced to
V
0
Zero-sequence component of the
voltage
kV
V
°
Rated operating voltage of primary
values/√3
V
1
Positive-sequence component of
the voltage
kV
V
°
Rated operating voltage of primary
values/√3
V
2
Negative-sequence component of
the voltage
kV
V
°
Rated operating voltage of primary
values/√3
I
0
Zero-sequence component of the
current
A
A
°
Rated operating current of the
primary values
I
1
Positive-sequence component of
the current
A
A
°
Rated operating current of the
primary values
I
2
Negative-sequence component of
the current
A
A
°
Rated operating current of the
primary values
9.4
Measured Values, Energy Values, and Supervision of the Primary System
9.4 Fundamental and Symmetrical Components
SIPROTEC 5, High-Voltage Bay Controller, Manual
999
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...