Operational Measured Values and Statistical Values
The following applies to the tolerances of currents and voltages:
•
The values apply both to the RMS values and the absolute value and phase angle of the fundamental
components.
•
The values were determined for pure sinusoidal signals – without harmonics.
Voltages
V
A
, V
B
, V
C
Voltage range
V secondary
< 200 V secondary
Secondary rated voltage
Measuring range
Frequency range
100 V to 125 V
(0.1 to 2) · V
rated
49 Hz to 51 Hz at f
rated
= 50 Hz
59 Hz to 61 Hz at f
rated
= 60 Hz
Tolerance
0.1 % of the measured value in the above mentioned
measuring range
Frequency range (expanded)
40 Hz to 60 Hz at f
rated
= 50 Hz
50 Hz to 70 Hz at f
rated
= 60 Hz
Tolerance
0.3 % of the measured value in the above mentioned
measuring range
V
AB
, V
BC
, V
CA
Voltage range
V secondary
< 200 V
Secondary rated voltage
Measuring range
Frequency range
100 V bis 125 V
(0.1 to 2) · V
rated
49 Hz to 51 Hz at f
rated
= 50 Hz
59 Hz to 61 Hz at f
rated
= 60 Hz
Tolerance
0.1 % of the measured value in the above mentioned
measuring range
Frequency range (expanded)
40 Hz to 60 Hz at f
rated
= 50 Hz
50 Hz to 70 Hz at f
rated
= 60 Hz
Tolerance
0.3 % of the measured value in the above mentioned
measuring range
Currents, Instrument Transformers
I
A
, I
B
, I
C
, 3I
0
Current range
A secondary
< 1:6 I
nenn
Rated currents
Measuring range
Frequency range
1 A, 5 A
(0.1 to 1.6) · I
rated
49 Hz to 51 Hz at f
rated
= 50 Hz
59 Hz to 61 Hz at f
rated
= 60 Hz
Tolerance
0.1 % of the measured value in the above mentioned
measuring range
Frequency range (expanded)
40 Hz to 60 Hz at f
rated
= 50 Hz
50 Hz to 70 Hz at f
rated
= 60 Hz
Tolerance
0.3 % of the measured value in the above mentioned
measuring range
11.46
Technical Data
11.46 Operational Measured Values and Statistical Values
SIPROTEC 5, High-Voltage Bay Controller, Manual
1195
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...