Protection Interface and Protection Topology
Setting Values
Mode
On
Off
PPS Synchronization
Telegr. and PPS
Telegr. or PPS
PPS synchronization off
Blocking of the unbalanced
runtimes
Yes
No
Maximum signal runtime threshold 0.1 ms to 30.0 ms
Increments of 0.1 ms
Maximum runtime difference
0.000 ms to 3.000 ms
Increments of 0.001 ms
Failure indication after
0.05 s to 2.00 s
Increments of 0.01 s
Transm. fail. alarm after
0.0 s to 6.0 s
Increments of 0.1 s
Max. error rate/h
0.000 % to 100.000 %
Increments of 0.001 %
Max. error rate/min
0.000 % to 100.000 %
Increments of 0.001 %
PPS failure indication after
0.5 s to 60.0 s
Increments of 0.1 s
Transmission Rate
Direct connection:
Transmission rate
2048 kbit/s
Connection via communication networks:
Supported network interfaces
G703.1 with 64 kbit/s
G703-T1 with 1.455 Mbit/s
G703-E1 with 2.048 Mbit/s
X.21 with 64 kbit/s or 128 kbit/s or 512 kbit/s
Pilot wires with 128 kbit/s
Transmission rate
64 kbit/s at G703.1
1.455 Mbit/s at G703-T1
2.048 Mbit/s at G703-E1
512 kbit/s or 128 kbit/s or 64 kbit/s at X.21
128 kbit/s for pilot wires
Transmission Times
Priority 1:
Response time, total approx.
For 2 ends
Minimum
8 ms
Typical
10 ms
For 3 ends
Minimum
10 ms
Typical
14 ms
For 6 ends
Minimum
15 ms
Typical
18 ms
Dropout times, total approx.
For 2 ends
Typical
20 ms
For 3 ends
Typical
20 ms
For 6 ends
Typical
26 ms
11.2
Technical Data
11.2 Protection Interface and Protection Topology
1104
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...