Grid Coupling Transformer
Addr.
Parameter
C
Setting Options
Default Setting
Winding 1
_:2311:101
General:Rated current
0.20 A to 100000.00 A
1000.00 A
_:2311:103
General:Rated voltage
0.20 kV to 1200.00 kV
400.00 kV
Winding 2
_:2311:102
General:Rated current
0.20 A to 100000.00 A
1000.00 A
_:2311:104
General:Rated voltage
0.20 kV to 1200.00 kV
400.00 kV
General
_:16351:1
90V V.contr.gc:Mode
•
off
•
on
•
test
on
_:16351:101
90V V.contr.gc:Oper-
ating mode
•
Manual
•
Auto
Manual
_:16351:157
90V V.contr.gc:Winding
selection
•
Winding 1
•
Winding 2
•
WithMaxLoad
Winding 1
_:16351:161
90V V.contr.gc:Winding
selection
•
Winding 1
•
Winding 2
Winding 1
Control tap changer
_:16351:107
90V V.contr.gc:Check
switching authority
•
no
•
yes
yes
_:16351:109
90V V.contr.gc:Control
model
•
direct w. normal secur.
•
SBO w. normal secur.
•
direct w. enh. security
•
SBO w. enh. security
SBO w. enh.
security
_:16351:110
90V V.contr.gc:SBO
time-out
0.01 s to 1800.00 s
30.00 s
_:16351:111
90V V.contr.gc:Feedback
monitoring time
0.01 s to 1800.00 s
10.00 s
Voltage Control
_:16351:164
90V V.contr.gc:Number
of target voltage
•
1
•
2
•
3
•
4
1
_:16351:112
90V V.contr.gc:Target
voltage 1 w1
10.000 V to 340.000 V
110.000 V
_:16351:165
90V V.contr.gc:Target
voltage 2 w1
10.000 V to 340.000 V
110.000 V
_:16351:166
90V V.contr.gc:Target
voltage 3 w1
10.000 V to 340.000 V
110.000 V
_:16351:167
90V V.contr.gc:Target
voltage 4 w1
10.000 V to 340.000 V
110.000 V
_:16351:146
90V V.contr.gc:Target
voltage 1 w2
10.000 V to 340.000 V
110.000 V
_:16351:168
90V V.contr.gc:Target
voltage 2 w2
10.000 V to 340.000 V
110.000 V
_:16351:169
90V V.contr.gc:Target
voltage 3 w2
10.000 V to 340.000 V
110.000 V
_:16351:170
90V V.contr.gc:Target
voltage 4 w2
10.000 V to 340.000 V
110.000 V
Control Functions
6.9 Voltage Controller
SIPROTEC 5, High-Voltage Bay Controller, Manual
507
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...