No.
Information
Data Class
(Type)
Type
_:300
Manual close:Detected
SPS
O
Settings
Addr.
Parameter
C
Setting Options
Default Setting
Ref. for %-values
_:2311:101
General:Rated normal
current
0.20 A to 100000.00 A
1000.00 A
_:2311:102
General:Rated voltage
0.20 kV to 1200.00 kV
400.00 kV
Breaker settings
_:2311:112
General:Current thresh.
CB open
1 A @ 100 Irated 0.030 A to 10.000 A
0.100 A
5 A @ 100 Irated 0.15 A to 50.00 A
0.50 A
1 A @ 50 Irated
0.030 A to 10.000 A
0.100 A
5 A @ 50 Irated
0.15 A to 50.00 A
0.50 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
0.100 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
0.500 A
_:2311:113
General:1-pole operate
allowed
•
no
•
yes
yes
_:2311:136
General:Op. mode BFP
•
unbalancing
•
I> query
unbalancing
Trip logic
_:5341:101
Trip logic:Trip at 2ph
short circuit
•
3-pole
•
1-pole, leading phase
•
1-pole, lagging phase
3-pole
_:5341:102
Trip logic:3-pole
coupling
•
with pickup
•
with trip
with trip
_:5341:103
Trip logic:Reset of trip
command
•
with I<
•
with I< & aux.contact
•
with dropout
with I<
Circuit break.
_:4261:101
Circuit break.:Output
time
0.02 s to 1800.00 s
0.10 s
_:4261:105
Circuit break.:Indicat. of
breaking values
•
with trip
•
always
always
Manual close
_:6541:101
Manual close:Action
time
0.01 s to 60.00 s
0.30 s
_:6541:102
Manual close:CB open
dropout delay
0.00 s to 60.00 s
0.00 s
Control
_:4201:101
Control:Control model
•
status only
•
direct w. normal secur.
•
SBO w. normal secur.
•
direct w. enh. security
•
SBO w. enh. security
SBO w. enh.
security
_:4201:102
Control:SBO time-out
0.01 s to 1800.00 s
30.00 s
_:4201:103
Control:Feedback moni-
toring time
0.01 s to 1800.00 s
1.00 s
5.6.8
Function-Group Types
5.6 Function-Group Type Circuit Breaker, 1-/3-Pole
SIPROTEC 5, High-Voltage Bay Controller, Manual
249
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...