For the Cyclic automatic reclosing function, 1 cycle is preset. The preset cycle cannot be deleted. You can add
and delete additional cycles from the function library in DIGSI 5.
[dwzykawe-100611-01.tif, 1, en_US]
Figure 7-21
Structure/Embedding of the Cyclic Automatic Reclosing Function
Automatic Reclosing Function with Adaptive Dead Time
The Automatic reclosing function with adaptive dead time (ADT) works without fixed disruption cycles
(
). The requirement for the usage of ADT is that voltage transformers on the line-side are
connected or there is a possibility to transfer a close command to a remote line end. With the ADT, the Auto-
matic reclosing function decides independently if and when an automatic reclosing is reasonable and permis-
sible and when it is not. The criteria is the phase-to-ground voltage, which is switched through after reclosing
from the opposite line end. The Automatic reclosing function with ADT occurs as soon as it is known that the
line from the opposite end has been placed back under voltage.
[dwaweasp-100611-01.tif, 1, en_US]
Figure 7-22
Structure/Embedding of the Automatic Reclosing Function With Adaptive Dead Time (ADT)
Operation with External Automatic Reclosing Function
The cooperation of an external reclosing device with the SIPROTEC protection device occurs through the func-
tion mode Operation with external automatic reclosing function (
). The function only provides
binary inputs for the influence of the protection functions in the SIPROTEC protection device. The external
automatic reclosing device delivers the close command. The SIPROTEC protection functions then provide for
the trip commands.
[dwextawe-100611-01.tif, 1, en_US]
Figure 7-23
Structure/Embedding of the Operating Function With External Automatic Reclosing Function
Function Control
The automatic reclosing function contains a central function control, see the following figure. You can find
detailed information on the function control in the section Function/Stage Control.
Protection and Automation Functions
7.2 Automatic Reclosing Function
SIPROTEC 5, High-Voltage Bay Controller, Manual
543
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...