Parameter: Only positive sequence
•
Default setting
(_:10621:103) Only positive sequence
=
no
With the parameter
Only positive sequence
, you set whether the positive-sequence system is to be
transmitted instead of 3 individual synchrophasors in the case of 3-phase measuring points. The setting you
make here is then valid for all PMUs with 3-phase measuring points.
Parameter: Class
•
Default setting
(_:10621:101) Class
=
Class P
With the setting
Class
, you set which performance class is used for the calculation of the measured values.
Class P
is the standard case for PMUs. In this case, filters are used that are suitable for a short response time
and therefore are well suited for recording dynamic processes.
Class M
is conceived for applications that are
unfavorably affected by alias effects and in which short response times are not relevant.
Parameter: Port
This parameter cannot be set because the Port results from the physical position where the corresponding
communication module is inserted.
Settings
Addr.
Parameter
C
Setting Options
Default Setting
Func. settings
_:10621:1
Func. settings:Mode
•
off
•
on
•
test
on
_:10621:101
Func. settings:Class
•
Class P
•
Class M
Class P
_:10621:102
Func. settings:Reporting
rate
•
1 frame/s
•
5 frames/s
•
6 frames/s
•
10 frames/s
•
12 frames/s
•
15 frames/s
•
20 frames/s
•
25 frames/s
•
30 frames/s
•
50 frames/s
•
60 frames/s
•
100 frames/s
•
120 frames/s
10 frames/s
_:10621:103
Func. settings:Only posi-
tive sequence
•
no
•
yes
no
_:10621:104
Func. settings:Port
•
port F
•
port E
•
port P
•
port N
results from the
plug-in module
position
_:10621:105
Func. settings:Custom-
ized phasor names
•
0
•
1
false
Meas.point V-1ph
_:10621:130
Func. settings:Meas-
uring-point ID
0to0
0
_:10621:131
Func. settings:Phasor
Freely editable text
9.5.9
Measured Values, Energy Values, and Supervision of the Primary System
9.5 Phasor Measurement Unit (PMU)
1018
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...