Information List
No.
Information
Data Class
(Type)
Type
Circuit break.
_:4261:500
Circuit break.:>Ready
SPS
I
_:4261:501
Circuit break.:>Acquisition blocking
SPS
I
_:4261:502
Circuit break.:>Reset switch statist.
SPS
I
_:4261:504
Circuit break.:>Reset AcqBlk&Subst
SPS
I
_:4261:503
Circuit break.:External health
ENS
I
_:4261:53
Circuit break.:Health
ENS
O
_:4261:58
Circuit break.:Position
DPC
C
_:4261:300
Circuit break.:Trip/open cmd.
SPS
O
_:4261:301
Circuit break.:Close command
SPS
O
_:4261:302
Circuit break.:Command active
SPS
O
_:4261:303
Circuit break.:Definitive trip
SPS
O
_:4261:304
Circuit break.:Alarm suppression
SPS
O
_:4261:306
Circuit break.:Op.ct.
INS
O
_:4261:307
Circuit break.:ΣI Brk.
BCR
O
_:4261:308
Circuit break.:ΣIA Brk.
BCR
O
_:4261:309
Circuit break.:ΣIB Brk.
BCR
O
_:4261:310
Circuit break.:ΣIC Brk.
BCR
O
_:4261:311
Circuit break.:Break.-current phs A
MV
O
_:4261:312
Circuit break.:Break.-current phs B
MV
O
_:4261:313
Circuit break.:Break.-current phs C
MV
O
_:4261:317
Circuit break.:Tripping current 3I0/IN
MV
O
_:4261:314
Circuit break.:Break. voltage phs A
MV
O
_:4261:315
Circuit break.:Break. voltage phs B
MV
O
_:4261:316
Circuit break.:Break. voltage phs C
MV
O
_:4261:322
Circuit break.:CB open hours
INS
O
_:4261:323
Circuit break.:Operating hours
INS
O
Trip Logic
Function Description
The Trip logic function block receives the group operate indication from the Protection function group or
Protection function groups and forms the protection trip command that is transmitted to the Circuit-breaker
function block.
The Circuit-breaker function block activates the device contact and thus causes the circuit breaker to open
(see
). The command output time is also effective here.
The trip logic also decides when the protection trip command is reset (see
[loausbef-140113-01.tif, 1, en_US]
Figure 5-18
Trip Command
5.5.5
5.5.6
5.5.6.1
Function-Group Types
5.5 Function-Group Type Circuit Breaker, 3-Pole
SIPROTEC 5, High-Voltage Bay Controller, Manual
213
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...