Checking Closing Conditions of Synchronous Systems
[losynsyn_adj_comm, 1, en_US]
Figure 6-76
Closing Conditions when Switching Synchronous Systems
The frequency difference is very low in the synchronous systems operating mode. It is below the threshold
value
f-threshold ASYN<->SYN
. The status is signaled via the
State f-synchronous
indication.
The parameters ΔV and Δα are checked for issuing a closure release (see
). The indication
All
sync. conditio. OK
signals that both setting values (conditions) are reached. If the conditions remain
fulfilled over the set time delay (parameter
Delay close command
), the release for closing is issued (see
also chapter
Every fulfilled condition is signaled individually via the indications
Voltage difference OK
and
Angle
difference OK
.
If a condition is not fulfilled, detailed information on why the condition is not fulfilled is provided via indica-
tions. If, for example, the differential voltage is outside the setting limits, the indication
V dif.too
large(V2>V1)
is issued. The indication indirectly contains information that the voltage V2 must be
increased for successful synchronization.
If the Expanded delta-f options stage type is configured and the parameter
(_:142) Limit dfdiff/dt
for asyn. op
is activated, the rate of change of the differential frequency is also checked. If the permissible
frequency change rate (parameter
(_:143) Max. value dfdiff/dt asyn
) is exceeded, the indication
(_:329) dfdiff/dt too large
is generated.
Control Functions
6.4 Synchronization Function
SIPROTEC 5, High-Voltage Bay Controller, Manual
389
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...