Signal Name
Description
Type
Default Value if
Signal Quality =
invalid
External health
The binary input
External health
reflects the
circuit-breaker status (EHealth).
This input will be set by the CFC using the BUILD_ENS
block. In turn, BUILD_ENS can query binary inputs that
represent the conditions
OK
,
Warning
, or
Alarm
(as
a result of the function Trip-circuit supervision).
ENS
Unchanged
Position
The signal
Position
can be used to read the circuit-
breaker position with double-point indication.
DPC
Unchanged
If the quality of the input signal assumes the status Quality = invalid, then the standby status (EHealth) of the
Circuit-breaker function block is set to
Warning
.
Table 6-6
Outputs of the Circuit-Breaker Function Block
Signal Name
Description
Type
Definitive trip
Protection has finally been tripped.
SPS
Alarm suppression
The signaling contact for external alarm inhibition is suppressed during
the runtime of automatic reclosing (optional) as well as during the
command output of switching commands.
SPS
Op.ct.
The information counts the number of switching cycles of the circuit
breaker.
INS
Trip/open cmd.
This logic output is responsible for the command output Off.
SPS
Close command
This logic output is responsible for the command output On.
SPS
Command active
The binary output
Command active
is responsible for signaling a
running command (relay active or selected switching device (SEL)).
SPS
CB open hours
The statistical value counts the hours the circuit breaker is open.
INS
Operating hours
The statistical value counts the hours where at least one phase current is
greater than the
Current thresh. CB open
parameter.
INS
Control
It is the task of the controls to execute command checks and establish communication between the command
source and the circuit breaker. Using the control settings, you specify how the commands are to be processed
(see also chapter
6.3.1 Command Checks and Switchgear Interlocking Protection
Through the function SBO (Select Before Operate, reservation
17
), the switching device is reserved prior to the
actual switching operation, thus it remains locked for additional commands. Feedback monitoring provides
information about the initiator of the command while the command is in process, that means, informing
whether or not the command was implemented successfully. These 2 options can be selected individually in
the selection of the control model, so that 4 combinations in total are available (see the following table).
The control makes the following settings available (see next table).
Parameters
Default Setting Possible Parameter Values
(_:4201:101) Control model
SBO w. enh.
security
18
direct w. normal secur.
SBO w. normal secur.
direct w. enh. security
SBO w. enh. security
(_:4201:102) SBO time-out
30.00 s
0.01 s to 1800 s
(Increment: 0.01 s)
17
In the IEC 61850 standard, reservation is described as Select before Operate (SBO).
18
This default setting is the standard control model for a switching command in an IEC 61850-compliant system.
Control Functions
6.2 Switching Devices
312
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...