background image

Synapse

 

 

MQTT/Modbus  TCP/8DI/8DO(R)/32x1-Wire/AC 

 

Industrial digital input/output module for 

remote process control and data acquisition 

 

Thank  you for  choosing our  product. The  7bit Synapse  module  designed  as  a  remot e 
Ethernet  DIO,  counter  and  1-Wire  temperature  input  module  for  industrial  
automation  and  monitoring  applications.  MQTT  connectivity  option  allows  you  to 
create  cloud-based  monitoring  &  control  applications.   Built-in  AC  power  supply  and 

2-port Ethernet  switch simplify  installation  and cabling,  extending  network  length  and 
allowing  to install  the  module  into existing  network  w/o  extra  equipment.   The  setup 
is made  easy  with  the web-config  page. 

     

 

Module  Synapse  is  an OPEN-TYPE  device.  It  should be  installed  in  a  control 

cabinet  free  of airborne  dust, humidity,  electric  shock and vibration 
 
The  device  is operating  at  dangerous  voltage  rating.  High  voltage  also  may  
occur  at  output  terminals  during  it  work.  Please  do  not  touch  these 
terminals  when  the device  is powered  on. DO NOT  connect AC power  to any 

of  input  terminals,  otherwise  serious  damage  may  occur.  Please  double 
check  all  wiring  before  Synapse  is getting  powered  up 
 
The  following  abbreviations  are  used  for  Modbus registers  functions:  C  - 

C

oils,  DI  - 

D

igital  Inputs,  HR/IR 

 

H

olding/

I

nput  Registers,  and  their  data 

format:  W  - 

W

ord  (2 bytes),  DW - 

D

ouble  Word,  b 

 

b

it.  R/W 

 

R

ead/

W

ri t e 

mode.   

 

1. Technical specifications 

 

Power  supply

 

100 - 220 VAC, 50/60 Hz, Max power  consumption:  3W

 

Communication

   

2 x Fast  Ethernet  switch,  Modbus TCP, MQTT

 

INPUTS

 

Points 

8 x DI with  single  common,   
Isolation  voltage  5000 Vac / 500 Vdc, 12 - 24 AWG 

Type 

24 VDC (SINK /  SOURCE)  or internal  isolated  DC supply 

Counters  & Time  on 
totalizers 

8 +  8 / 8 +  8 (for each  DI & DO channel),  32-bit capacity, 
static  memory,   1 kHz max.  sw.  frequency 

Jitter  filter 

Individual  for each  channel,  adj.   0 ~  20ms (default 20ms) 

OUTPUTS

 

Points 

8xDO, 12 - 24 AWG, two  groups DO 1 - 4 and DO 5 - 8 
(SSR  or Relay  or SSR  + Relay) 

Relay 

220 VAC /  30 VDC, 2A. 
Max.  frequency:  1 Hz, ~10 ms response  time 

SSRs* 

AC,  85 - 220V 2A, Zero-crossing  switching. 
Max.  frequency:  100 Hz 

1WIRE

 

Points 

Up to 32 digital  thermometers  DS18B20 

Bus length 

Up to 200 m. 

ENVIRONMENTAL

 

Operation  - 
Storage  /  Protection 

0°C 

55°C, 5 

- 90% (w/o  condensation),   -

25°C 

70°C, 5 

- 95%   

IP40 

Weight 

200 g. 

made  by  order 

 
2. Dimensional drawing 
 

 

 

 
 
3. Wiring

 

 
3.1 Ethernet

. Synapse  has an embedded  switch which  make  easy  to connect numerous  

modules  simply,  connecting  them  to each  other  in "daisy  chain". As it  is true  Ethernet  

witch,  each  connection  may  be  up to 100 m.  It  is  also possible  to connect  the  devic e 
at  any breaking  of existing  Ethernet  link. 
 

 
 
 
 
 

 

3.2 Digital  inputs   
 

 
 
 
 
 
 
 
 
 
 

 

 

Use  internal  power  supply  for  powering  inputs  via  long  cables  with  caution      
due  to low  voltage  and voltage  drop you may  have  unstable  DI signaling 

 

 

3.3 Digital  outputs 

There  are  2 groups by 4 outputs, each  can  be either  relay  or SSR 

(by order)  type.  Due  to Zero-cross  detection  unit,  SSR provides  comfort  switching  for 
any  AC load  in the  range  85 - 220V, 2A. Relay  outputs is commonly  used for dry 
contacts and  DC signals commutation.   

 

 

To  avoid sparks,  limit  switching  currents  and increase  switching  lifetime  for 
the  outputs, it  is  strongly  recommended  to  use  extra  snubber  circuits  for 
inductive  loads.   

 
3.4  Safe  power  on 

After  power  on the  module  can  restore  its  outputs to  a  previous  

state.  For  many applications  it is convenient  feature,  but for some not. E.g.  some parts  
of a heavy  machine  may  accidentally  move  on repower  and cause dangerous  situation. 
To  avoid  this  problem  now  there  is  a  special  setting  to  choose  output  state  after 
repower: 
 

Address

 

Description

 

Data

 

R/W 

Default 

HR35 

Safety  state  0 

 off,  1 - on 

R/W 

0 (off) 

 
3.5  PWM  for  triac  outputs 

The  duty cycle  is  set  as 0  ..  100 which  means  how  many  

periods  of AC current  from one  hundred  will  power  the  load.  So the  time  base  of the 
PWM  is 100 *  20 ms  (1/50Hz)  =  2  seconds.  Before  using  DO  for  common   ON 

  OFF 

control set  PWM values  to 0. 

Address

 

Description

 

Data 

 

R/W 

Default 

DI0 ~  DI7 

Digital  Inputs 

HR20 ~ HR27 

Input filters  (0 - disabled) 

R/W 

20 

Address

 

Description

 

Data 

 

R/W 

Default 

C0 ~  C7 

Digital  outputs 

R/W 

Internal 

supply  