background image

INSTRUCTION

 

AND

 

PROGRAMMING

 

MANUAL

 

 

 

TLIC

 

is

 

used

 

in

 

conjunction

 

with

 

2

 

wire

 

or

 

4

 

wire

 

transmitter

 

for

 

remote

 

indication

 

and

 

control

 

 

 

 

Ensure

 

that

 

no

 

physical

 

damage

 

is

 

caused

 

to

 

TLIC

 

due

 

to

  

during

 

transit.

  

 

Connect

 

power

 

supply

 

to

 

controller

  

 

Connect

 

transmitter/

 

calibrator

 

output

 

of

 

4

20mA

 

to

 

I/P

 

terminals

 

of

 

TLIC

 

with

 

multi

meter

 

in

 

series.

  

 

Switch

 

on

 

the

 

supply,

 

observe

 

display

 

shows

 

some

 

readings.

 

 

Adjust

 

input

 

of

 

4mA

 

and

 

display

 

shoes

 

lowest

 

value.

 

 

Increase

 

I/P

 

gradually

 

from

 

4

 

to

 

20mA

 

&

 

observe

 

increase

 

in

 

displayed

 

value

 

to

 

its

 

maximum.

  

 

 

 

During installation, please ensure… 

 

Identify

 

mounting

 

location

 

away

 

from

 

high

 

voltage

 

cables,

 

contactors.

 

 

The

 

ambient

 

temp

 

around

 

location

 

should

 

be

 

maintained

 

below

 

50

C

  

 

TLIC

 

Should

 

be

 

protected

 

from

 

direct

 

sunlight

 

by

 

using

 

sun

 

shield.

 

Panel

 

Mtd

 

(Fig

 

1)

 

  

Prepare

 

92

 

x

 

92

 

mm

 

cutout

 

on

 

panel

 

and

 

mount

 

the

 

TLIC

 

from

 

front

 

and

 

secure

 

it

 

in

 

place

 

through

 

fixing

 

clamps.

 

 

Wall

 

Mtd

 

(fig

 

2)

 

  

Mounting

 

surface

 

should

 

be

 

flat

 

and

 

without

 

vibrations

 

Drill

 

holes

 

at

 

appropriate

 

location.

 

Mount

 

TLIC

 

on

 

identified

 

location

 

and

 

secure

 

it

 

on

 

four

 

mounting

 

hole.

 

 

 

 

During

 

wiring,

 

supply

 

should

 

be

 

kept

 

off

 

for

 

human

 

safety

 

&

  

 

prevention

 

of

 

accidents.

  

 

Connect

 

230VAC

 

to

 

supply

 

terminal

 

of

 

TLIC.

 

In

 

case

 

of

 

24VDC

 

supply,

 

ensure

 

correct

 

polarity.

 

 

Connect

 

4

20mA

 

output

 

of

 

2

 

wire

 

transmitter

 

to

 

input

 

terminals

 

of

 

TLIC

 

in

 

series

 

with

 

24

 

V

 

DC

 

o/p

 

terminals

 

(refer

 

fig

 

3).

 

Ensure

 

distance

 

between

 

transmitter

 

&

 

TLIC

 

does

 

not

 

exceed

 

500

 

Ohm

 

(Max

 

load)

  

 

Whenever

 

Re

transmission

 

is

 

provided,

 

it

 

is

 

isolated

 

type

 

(

 

max

 

load

 

400

 

ohms)

 

  

Techtrol

 

Level

 

Indicator

 

Controller

 

–TLIC

  

                   

 

 

Pre

 ‐ 

installation

 

check

 

 

Pre

in

 

Installation

  

 

Termination

 

and

 

Wiring

 

 

Panel

 

Mounted

 

IP41

Wall

 

Mounted

 

IP65

 

/

 

Exd

 

IIB

92

92

SIDE VIEW

8

134

PANEL CUTOUT

CC 259.

5m

m

4xØ8.5 

CC 169.5mm

Mounting Details

   

Panel

 

Mounted

                                               

Fig

 

1

Wall

 

Mounted

                                                

Fig

 

2

Summary of Contents for TLIC

Page 1: ...e 92 x 92 mm cutout on panel and mount the TLIC from front and secure it in place through fixing clamps Wall Mtd fig 2 Mounting surface should be flat and without vibrations Drill holes at appropriate location Mount TLIC on identified location and secure it on four mounting hole During wiring supply should be kept off for human safety prevention of accidents Connect 230VAC to supply terminal of TL...

Page 2: ...tus i e LED ON RELAY ON Modes of operation Program Mode In this mode user can program the unit for measuring span bottom offset relay set reset points Run Mode In this mode unit will be ON and reads the level Panel Mounted Programming Key Functions Wall Mounted E 24VDC Supply 24VDC Supply Level Display Alarm LED Indication Keypad Unit Sticker TLIC Panel Front Bezel Function Key to enter in program...

Page 3: ...position as required 1 6 0 0 1 0 0 0 Level Range Value Edited Level Range L r g B o F 0 1 0 0 0 0 0 0 Bottom Offset Value Edited Bottom Offset F F r S t 4 D o t 0 0 0 0 0 0 8 0 5 Reset value of relay 4 Edited reset value of relay 4 Decimal point position New decimal pt position RUN MODE DISPLAY S E t 4 0 0 0 0 0 8 0 0 Set value of relay 4 F F F Edited set value of relay 4 r S t 1 0 0 0 0 0 1 0 5 R...

Page 4: ...ion 2 Connect 24 VDC with correct polarity 3 Check supply is within limit Replace fuse F1 500mA for 230VAC 2 No change in display value 1 No change in signal from X mitter 2 Wrong connection 1 Problem in transmitter 2 Check and connect X mitter with correct polarity 3 Fluctuation in display value 1 O P of X mitter is fluctuating 2 Turbulence in liquid 1 Check tighten loose connections if any 2 Ins...