Range
:
0
to
9999
Decimal
Position
:
Selectable
Accuracy
:
0.25%
FSD
Display
:
0.5”,
4
digits,
seven
segment
LED
Programming
:
Through
keypad
No
of
Set
Points
:
Four
Power
Supply
:
90
‐
270VAC
or
24VDC
±
10%
Supply
to
transmitter
:
24VDC
@30mA
Input
:
4
‐
20mA
Output
:
4
Relays
x
SPDT,
5A
250VAC
Power
:
15VA
LED
Indication
:
Green
‐
Supply,
Red
‐
Level
set
point
Level
LED
Status
:
LED
On=
Relay
On
Enclosure
:
1)
ABS
plastic
IP41
panel
mtg
Size:
96
x
96
x
134(D)
mm
2)
Cast
Al.
IP65
/
Exd
Gr.
IIB
wall
mtg.
Size:
275
(L)
x
185
(W)
x
175(D)
mm
Special
Feature
:
Retransmission
o/p
(4
‐
20
mA)
isolated
Amb.
Temp
:
0
‐
55
⁰
C
Humidity
:
90%
Non
‐
condensing
.
SL
Problem
Cause
Solution
1
No
Display
1.
Improper
supply
or
loose
connection
2.
Wrong
supply
polarity
in
case
of
24VDC
3.
Fuse
blown
1.
Check
supply
&
tighten
loose
connection
2.
Connect
24
VDC
with
correct
polarity
3.
Check
supply
is
within
limit.
Replace
fuse
(F1)
(500mA
for
230VAC)
2
No
change
in
display
value.
1.
No
change
in
signal
from
X'mitter.
2.
Wrong
connection
1.
Problem
in
transmitter
2.
Check
and
connect
X'mitter
with
correct
polarity
3
Fluctuation
in
display
value.
1.
O/P
of
'X'mitter'
is
fluctuating
2.
Turbulence
in
liquid
1.
Check
&
tighten
loose
connections
if
any
2.
Install
X'mitter
at
turbulent
free
location
5
Incorrect
Relay
Operation
1.
Incorrect
Relay
Setting
1.
Recheck
and
program
for
correct
set
&
reset
values
6
Re
‐
transmission
current
not
proper
1.
Incorrect
programming
for
re
‐
transmission
2.
Improper
wiring
1.
Recheck
programmed
values
2.
Refer
‘Termination
&
Wiring’
for
correct
wiring
Troubleshooting
MAN/TLIC /REV 03/06
‐
19
Specifications
PUNE TECHTROL PVT. LTD
S-18, MIDC Bhosari, Pune: 4110026 India
Ph: +91-20-66342900,
, www.punetechtrol.com
Works: J-52/7, MIDC, Bhosari, Pune - 411026. India +91-20-67313600