BASIC OPERATING INSTRUCTIONS FOR THE MA3000 FIRE CONTROL PANEL

WITH THE CF3000LCD KEYPAD.

Note: Text in quotes indicates a displayed message; messages preceded and followed by asterisks indicate additional

related message(s) to follow. Buttons markings are shown in brackets ( [ ] ).

Note: This system uses a “smart” menu-driven keypad; that is,
when scrolled, the keypad will display only those options that
are relevant to the existing condtion.

STANDBY

This is the normal mode. The keypad will read “NORMAL’; no

reminders (“DISABLE”; “FIRE/TEL”; “SYS TEL”) will display; the
green AC-POWER light will be on.

FIRE ALARM

Signal deviceswill sound. The keypad will display “

∗∗

FIRE

∗∗

”,

followed by the number and description of the zone in alarm,
then “

∗∗

FIRE STATUS

∗∗

”, then “FIRE ALARM”. The “FIRE/TBL”

reminder and the ALARM light will come on.

SILENCING A FIRE ALARM

Enter code and press [SILENCE] to silence the signal devices

and keypad sounder. The keypad will display “FIRE SI-
LENCED, followed by “

∗∗

FIRE STATUS

∗∗

”, “FIRE ALARM”,

then “FIRE SILENCED”. Another alarm will sound the signals
again.

FIRE ALARM RESET

Enter code and press [INFO]. Press [NO] to continue to scroll

options or [YES] to select option.

FIRE TROUBLE

The keypad will display “FIRE TROUBLE” followed by the

number and description of the zone in trouble, then “

∗∗

FIRE

STATUS

∗∗

”, then “FIRE TROUBLE”. The “FIRE/TBL” reminder

will flash.

FIRE TROUBLE RESET

Enter code and press [INFO]. The keypad will display options

one at a time. Press [NO] to continue to scroll options or [YES]
to select option.

SUPERVISORY ALARM

The keypad will sound and display “

∗∗

SUPV ALARM

∗∗

” fol-

lowed by the number and description of the fire supervisory
zone in alarm, then “

∗∗

FIRE STATUS

∗∗

”, then “SPRINK SUPV

ALARM”. This indicates that a device designed to monitor the
fire alarm system is in alarm.

SUPERVISORY TROUBLE

The keypad will sound and display “

∗∗

SUPV TROUBLE

∗∗

followed by the number and description of the supervisory zone
in trouble, then “

∗∗

FIRE STATUS

∗∗

”, then  “SPRINK SUPV

TRBL”.

SUPERVISORY ALARM/TROUBLE RESET

Enter code and press [INFO].The keypad will display options

one at a time. Press [NO] to continue to scroll options or [YES]
to select option.

FIRE ALARM/TROUBLE CONDITIONS

The keypad will constantly display the alarm/trouble condi-

tions still present on the system. “

∗∗

FIRE STATUS

∗∗

” will dis-

play followed by the condition(s). To determine the particular
zone(s) respansible for the condition(s), enter code and press
[INFO]. The keypad will display options one at a time. Press
[NO] to continue to scroll options or [YES] to select option.

DISABLE/ENABLE ZONE BUTTON

For installer’s use only.

ALARM TEST

Operate an initiating device. Signal devices will sound and the

keypad will display an alarm. Silence the alarm and reset the
device.

FIRE DRILL TEST

Enter code and press [INFO]. Press [NO] until “FIRE DRILL?

(YES/NO)” appears, Press [YES]. The fire signal devices
should sound. To terminate the test, enter code, then press
[SILENCE]. The keypad will display “NOT NORMAL”, indicating
that the fire bell is active.

SYSTEM TEST

To test the keypad, hold down the[*] and [3] keys simul-

taneously. The three reminders (“DISABLE”; “FIRE/TEL”; “SYS
TBL”) will display and all screen characters will appear black.
Holding the [

] key depressed, press [3] to view different

characters on the display. Press [RESET] to terminate the test.

To test fire alarm signal devices, enter code and press

[INFO]. Press [NO] until “TEST ALARMS? (YES/NO)” appears.
Press [YES]. Fire signal devices should sound for 2 seconds.

SYSTEM TROUBLE

When a system trouble is detected, the “SYS TBL” reminder

will flash, the screen will display the system trouble, and the
keypad sounder will pulse. To acknowledge the system trouble,
enter code, then press [RESETI. The keypad will silence and
the system trouble descrIption will clear. However If the system
trouble still exists, the “SYS TEL” reminder will remain on and
the screen will display “NOT NORMAL”.

To determine the particular condition responsible for the

system trouble, enter code, then press [INFO]. Press [No] until
“DISP SYS TRBL? (YES/NO)” appears, then press [YES].

WI658C  08/99

Local Service Representative: ________________________________________________________

Address: _________________________________________________________________________

Telephone Number: ________________________________________________________________

Note: (1) Test system weekly! (2) If panel sounder is on, call for service. (3) A complete functional checkout of the control unit is required
           following any programming or reprogramming. (4) This page is to be framed and mounted adjacent to the control unit.