background image

IMT400-09

www.ueonline.com

400 Series

Temperature Controls

Types: B400, B402, B403, C400, 

 

C402,C403, E400, E402, E403,

 

F400, F402, F403 

U N I T E D   E L E C T R I C 

C O N T R O L S

Installation and Maintenance 

Instructions

Please read all instructional literature carefully and thoroughly before starting.  Refer to the final page for the listing of Recommended 
Practices, Liabilities and Warranties.

IMT400-09

GENERAL

The 400 Series temperature switch utilizes either a liquid filled sensing stem 

(immersion stem, direct mounting) or liquid filled sensing bulb (bulb & 
capillary, remote mounting) to detect a temperature change.  The response 
at a predetermined set point(s) actuates one, two or three snap-acting 
switches, converting the temperature signal into an electrical signal.  Control 
set point(s) may be varied by turning an internal calibrated pointer and 
dial (B & E type) or internal adjustment screw (C & F) according to the 
procedures outlined (See Part II – Adjustments)

THESE PRODUCTS DO NOT HAVE ANY FIELD REPLACEABLE PARTS.

MAXIMUM TEMPERATURE* STATED IN LITERATURE AND ON 

NAMEPLATE MUST NEVER BE EXCEEDED, EVEN BY SURGES IN 

THE SYSTEM.  OCCASIONAL OPERATION OF UNIT UP TO MAX. 

TEMPERATURE IS ACCEPTABLE (E.G., START-UP, TESTING).  CONTINUOUS 

OPERATION SHOULD BE RESTRICTED TO THE DESIGNATED ADJUSTABLE 

RANGE.

*Maximum Temperatures - the highest temperature to which a sensing 

element may be occasionally operated without adversely affecting set point 

calibaration and repeatability.

Please refer to the product bulletins for product specifications.  Product 

bulletin may be found at www.ueonline.com

PART I - Installation

Tools Needed

 

Flathead Screwdriver 

 Hammer (for alternative wire knockouts) 

 Adjustable wrench

MouNTING

ALwAYS LOCATE UNITS wHERE SHOCk, VIBRATION AND 
TEMPERATURE FLUCTUATIONS ARE MINIMAL.  DO NOT MOUNT UNIT 

IN AMBIENT TEMPERATURES EXCEEDING PUBLISHED LIMITS.

400 SERIES TEMPERATURE CONTROLS CAN BE MOUNTED IN ANY 
POSITION, PROVIDED THE ELECTRICAL CONDUIT IS NOT FACING UP.  

THE PREFERRED MOUNTING POSITION IS VERTICAL (TEMPERATURE 

CONNECTION FACING DOwN), SPECIFICALLY wHERE HEAVY CONDENSATION IS 

EXPECTED.

For remote mounting, mount the unit via the (2) 1/4” screw clearance holes 
on the enclosure (see dimensions). Fully immerse the bulb and 6” of capil-
lary in the control zone. It is generally desirable to place the bulb close to the 

heating or cooling source in order to sense temperature fluctuations quickly. 

Be sure to locate the bulb so that it will not be exposed to temperatures 

beyond the instruments range limits.

ALwAYS HOLD A wRENCH ON THE IMMERSION STEM HEX wHEN 
MOUNTING UNIT. DO NOT TIGHTEN BY TURNING ENCLOSURE. THIS 

wILL DAMAGE SENSOR AND wEAkEN SOLDERED OR wELDED 

JOINTS.

On models supplied with an external manual reset button, be sure to leave 

sufficient finger space over the reset button for the operator to reset the 

control.

WIRING

DISCONNECT ALL SUPPLY CIRCUITS BEFORE wIRING UNIT.  wIRE 

UNITS ACCORDING TO NATIONAL AND LOCAL ELECTRICAL CODES.  

MAXIMUM RECOMMENDED wIRE SIzE IS 14 AwG.  THE RECOM-

MENDED TIGHTENING TORqUE FOR FIELD wIRING TERMINALS IS 7 TO 17 

IN-LBS.

ELECTRICAL RATINGS STATED IN LITERATURE AND ON NAMEPLATE 
SHOULD NEVER BE EXCEEDED. OVER-LOAD ON A SwITCH CAN CAUSE 

FAILURE ON THE FIRST CYCLE.  

Remove the two screws retaining the cover and cover gasket, a 3/4” NPT E/C 
is provided on the right of the enclosure in addition to the two (2) cast-in 7/8” 

diameter knockouts for 1/2” electrical conduit that are located on the left side 

and rear of the enclosure. These can easily be knocked out by placing the 

blade of a screwdriver in the groove and tapping sharply with a hammer.  

Connect conduit to the enclosure and wire directly to the switch terminals 
according to local and national electrical codes.  Bring the wires up to 

terminals from the rear of the enclosure. (See Figure 1.) If manual reset 

switch or DPDT options are used, lead wires are supplied, color coded as 

follows:

Manual Reset Option 1530 

(for 400)

Manual Reset Option 1530 

(for 402)

Switch 1

Switch 1

Switch 2

C

Violet

Violet

Yellow

NO

Blue

Blue

Orange

NC

Black

Black

Red

Reviews: