Installation guide

Pressure operated water valve

 

WVS 32 – WVS 100

016

R9

55

6

016

R9

55

6

© Danfoss | DCS (az) | 2018.02

DKRCC.PI.DA0.A8.52 | 1

WVS 32

WVS 40

WVS 50 - WVS 100

16

17

18

19

19

9

Fig. 1

Fig. 2

Fig. 3

Fig. 4

Fig. 5

ENGLISH

Pressure operated water valve, 

types WVS 32 – WVS 100
Technical data

Media

Refrigerant side

R22, R1270, R134a, R290, R404A, 

R407A, R407C, R407F, R410A*, 

R448A, R449A, R450A, R452A, 

R507A, R513A, R600, R600a, R717
* High pressure refrigerants version 

(45, 2 MWP) only

Water side

Fresh water and brine

Max. test pressure

Refrigerant side

P

e

= 29 bar = 2900 kPa

R410a/R744 (CO

2

)

P

e

= 60 bar = 6000 kPa

Water side

P

e

= 16 bar = 1600 kPa

Opening differential pressure

WVS 32 – WVS 40

Min. 0.5 bar = 50 kPa
Max. 4 bar = 400 kPa

WVS 50 – WVS 100

Min. 0.3 bar = 30 kPa
Max. 4 bar = 400 kPa

For complete list of approved refrigerants, 

visit 

www.products.danfoss.com

 and search 

for individual code numbers, where  

refrigerants are listed as part of technical 

data.

Fig. 1–3

  1.  Flare connection

  2.  Weld nipple

  3.  Bellows element

  4.  Push rod

  5.  Regulating nut

  6.  Top part

  6a.  Cover

  7.  Pilot insert 

  8.  Spindle

  9.  Teflon sleeves

10.  Insulating disc

10a. Gasket 

 

12.  Valve cover 

15.  Servo piston 

 

*)

16.  Bottom screw

17.  Drain plug 

18. Gasket 

19.  Strainer assembly, complete  *)

20.  Self-cleaning strainer

21.  Pilot nozzle 

24.  Servo spring 

 

**)

*)   Please state valve size

**)  See table Fig. 6

Assembly

Screws connecting pilot unit with 

valve body to be tighten with 8.5 Nm.

Fitting

WVS is to be fitted in the cooling water 

inlet with flow in the direction of the 

arrow and with the bellows element 

facing upwards. It is recommended 

that a strainer should be inserted 

before the valve.

The bellows element is to be 

connected to the pressure side of 

the refrigeration system at a point 

where pressure pulsations from the 

compressor do not affect the valve, 

e.g. on the top of the condenser or 

after the oil separator. The pressure 

line must be connected so that 

impurities cannot enter it. See Fig. 5.

Do not remove white insluting disk 

(10). It needs to be always fitted

between pilot element and valve 

housing.

Setting

Remove the cover (6a). 

WVS can be set to begin opening

at a condensing pressure of 

min. 2.2 bar = 220 kPa and 

max. 19 bar = 1900 kPa.

Summary of Contents for WVS 32

Page 1: ...ment 4 Push rod 5 Regulating nut 6 Top part 6a Cover 7 Pilot insert 8 Spindle 9 Teflon sleeves 10 Insulating disc 10a Gasket 12 Valve cover 15 Servo piston 16 Bottom screw 17 Drain plug 18 Gasket 19 Strainer assembly complete 20 Self cleaning strainer 21 Pilot nozzle 24 Servo spring Please state valve size See table Fig 6 Assembly Screws connecting pilot unit with valve body to be tighten with 8 5...

Page 2: ... Pe 29 bar 2900 kPa R410a R744 CO2 Pe 60 bar 6000 kPa Vandside Pe 16 bar 1600 kPa Åbningsdifferenstryk WVS 32 WVS 40 min 0 5 bar 50 kPa maks 4 bar 400 kPa WVS 50 WVS 100 min 0 3 bar 30 kPa maks 4 bar 400 kPa For komplet liste over godkendte kølemidler besøge www products danfoss com og søg efter individuelle bestillingsnumre hvor kølemidler er opført som en del af tekniske data Fig 1 3 1 Flaretils...

Page 3: ...eschlossen wo vom Kompressor herrührende Druckpulsationen das Ventil nicht beeinflussen können z B zuoberst am Verflüssiger oder hinter dem Ölabscheider Das Druckrohr ist so anzuschliessen daß etwaige Schmutzteilchen nicht in das Rohr gelangen können Siehe Abb 5 Isolierscheibe 10 nicht entfernen Diese muss immer zwischen dem Einstellelement und dem Ventilgehäuse montiert sein Einstellung Deckel 6a...

Page 4: ...Réglage Enlever le couvercle 6a La WVS peut être réglée pour commencer à s ouvrir à une pression de condensation de min 2 2 bar 220 kPa et au maxi 19 bar 1900 kPa La vanne est complètement ouverte quand la pression de condensation s est élevée de 1 bar 100 kPa au dessus de la pression d ouverture de réglage Une pression de condensation plus basse est obtenue en tournant l écrou de réglage 5 vers l...

Reviews: