background image

35(0,(56;

),5($/$50

&21752/3$1(/

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

86(50$18$/

0$,17(1$1&(*8,'( 

/2*%22.



 

 

Summary of Contents for Premier SX

Page 1: ...35 0 5 6 5 50 21752 3 1 86 5 0 18 0 17 1 1 8 2 22...

Page 2: ...ALARM SOUNDERS 5 3 NEW ZONE IN ALARM 5 4 MANUALLY ACTIVATING THE ALARM SOUNDERS 5 5 RESETTING THE PANEL 6 Fault Conditions 8 6 1 DIFFERENT TYPES OF FAULT 6 2 IN THE EVENT OF A FAULT CONDITION 7 Disabl...

Page 3: ...Brigade of the Fire Condition An Auxiliary Output normally used to trigger local fire fighting equipment such as magnetic door release systems to automatically close fire doors plant shutdown systems...

Page 4: ...em is in operation 28 4 1 b notices are displayed in all areas where detectors are sited 28 4 2 c contractors take appropriate precautions while working in protected areas 28 4 3 d precautions against...

Page 5: ...e on the opposite page The only functions that can be performed by the User when the Panel is in its Normal state are Overriding any Delays which may have been programmed into the Panel by pressing th...

Page 6: ...STEADYYELLOW A processor fault has occurred To reset turn keyswitch on then back off If problem persists consult your dealer GEN FIRE ONLY STEADYRED A manual evacuation has occurred The sounders will...

Page 7: ...The Alarm Sounders and the Panel s Internal buzzer will cease to sound but the light s for the Zone s in Alarm and the red General Fire light will stay lit All other Alarm outputs i e the Auxiliary Fi...

Page 8: ...ht which conveys more precise information on the type of Fault detected If this light is lit by itself it indicates a keyswitch fault Zone Fault The relevant Zone Fault light flashes when there is a w...

Page 9: ...d position Note the Fault s down in the Log Book at the back of this Manual and take appropriate action to correct it them See User Responsibilities section on Page 5 When a fault has been rectified t...

Page 10: ...again and this will cause Zone 1 Disablement LED to light steady 5 Pressing scroll No 4 switch will cause the zone disablement LED to toggle to zone 2 and so on 32 5 1 5 1 8 7 6833 7 6 67 0 7 1 6 1 2...

Page 11: ...a zone processes an alarm signal the panel will indicate fire in the usual way but the sounders will not be active until the delay period has expired To override this delay press Delay Override Switc...

Page 12: ...Yes No Yes No Yes No LENGTH OF DELAY 1 TO 9 MINUTES IF APPLICABLE OUTPUT ROUTING INFORMATION TYPE OF OUTPUT CONNECTED WHAT HAPPENS WHEN ACTIVATED Auxiliary Output Yes No Fault Output Yes No ADDITIONAL...

Page 13: ...ding fire alarm conditions failures tests temporary disconnections disablements enablements dates of installing engineers visits together with a note of any outstanding work or conditions You are advi...

Page 14: ...REMIER SX USER MANUAL MAINTENANCE GUIDE LOG BOOK Approved Document No GLT MAN 102T PAGE 14 Issue 1 1 Authorised GH Date 06 11 02 DATE TIME ZONE BRIEF DETAILS OF EVENT ACTION REQUIRED COMPLETED INITIAL...

Page 15: ...ce with EN54 1 26 4 for compliance The PSE mains feed from a 3A spur should be checked The PSE Charger voltage should be checked adjusted if necessary 27 8V with batteries disconnected The battery vol...

Page 16: ...______________________________________________________________________________________ _______________________________________________________________________________________________ _________________...

Page 17: ...35 0 5 6 5 50 21752 3 1 167 7 21 0 18...

Page 18: ...BATTERY POWER 8 4 1 CONNECTING MAINS POWER 4 2 CONNECTING THE BATTERIES 5 DEVICE TERMINATION 9 5 1 CONNECTING THE DETECTOR SOUNDER CIRCUITS 5 2 CONNECTING THE AUXILIARY INPUTS AND OUTPUTS 6 SOUNDER AC...

Page 19: ...ondensing It will withstand vibrations between 5 150 Hz It has a maximum capacity of 32 devices per zone The PSE is linear with a 1 1A output at system voltage 18 32V The mains supply is filtered befo...

Page 20: ...erly terminated at the Panel However the System specification may demand the use of a particular type of cable and due regard should be paid to this fact 2 2 MAINS WIRING The requirement for the Mains...

Page 21: ...ers own instructions The wiring for each Detector circuit should be connected to the relevant termination block on the Main Control PCB and their screens terminated at the Panel s base earth tag see p...

Page 22: ...is no fault and open when there is a fault This should be taken into account when any device is connected to the fault relay Typical auxiliary output wiring 12 0 1 8 7 5 8 7 1 7 21 9 127 7 1 217 7 6...

Page 23: ...ble gland Any unused knockouts must be securely blanked off It is essential that the 230Va c Mains cable is fed into the enclosure via one of the inlets at the top right hand corner of the enclosure F...

Page 24: ...les to help minimise mains interference Once the mains is connected the protective cover should be replaced BEFORE turning on the mains power This will minimise the chance of electric shock from the P...

Page 25: ...the steel EMC cable grounding plate Incoming Detector and Sounder circuits should be connected to the relevant connector block on the Main Control PCB as shown in Figure 6 below All screens should be...

Page 26: ...ing triggered to its Alarm sounder outputs being activated can be programmed into the panel by the Engineer This is a particularly useful feature for schools nightclubs and other public places where t...

Page 27: ...continue running but doesn t want spurious false alarms The panel will respond in the usual manner to any events in any non disabled zones 7 2 TO PROGRAMME ZONE OR SOUNDERS AS DISABLED Any number of...

Page 28: ...mode 6 Once testing of that zone is completed press scroll button to move to another Zone or turn the control key switch to off position to exit test mode 9 GENERAL FAULT FINDING 9 1 ZONE FAULTS Open...

Page 29: ...rong Charging Voltage The charging voltage should be 28 4V off load at 25 o C If it has been altered reset using potentiometer VR1 5 Overcharged Batteries Remove the batteries and measure the voltage...

Page 30: ...zone devices As a guideline the quiescent current of most modern detectors is typically 0 00005A 50uA and that of manual call points is zero To obtain the most accurate figures consult the devices ma...

Page 31: ...ivate sounders 12 FIRE RELAY NO CM NC Activates on fire including test mode 13 FAULT RELAY NO CM NC Normally powered ie NO is closed with no fault 14 BATTERY Connect 2 x 12V SLA batteries in SERIES ie...

Page 32: ...OMINAL 18 32 V SYSTEM VOLTAGE RIPPLE 2V PK PK MAX CHARGER SIZE UP TO 7AH in 24 Hours ZONE VOLTAGE 21V DC NOMINAL 20 22 5V SOUNDER ALARM OUTPUTS 2 x 400mA 24V DC Nominal AUXILIARY FAULT OUTPUT 1 x RELA...

Reviews: