background image

BASIC INSTALLATION

Be sure to select a control panel installation site that is not easily

accessible to intruders. Leave at least 2" around the panel box to

permit adequate ventilation/heat dissipation. The installation loca-

tion should be dry, in close proximity to an AC source and a

ground connection.

The printed circuit board, mounting hardware and keypad should

be removed from the packaging inside panel box. Press the four

white nylon mounting studs into cabinet from the back prior to

mounting the cabinet. Before mounting the circuit board on the

back of the cabinet, pull all cables into cabinet and prepare them

for connection. Then attach circuit board to mounting studs.

Connect all zones with the 1KOHM EOL resistors supplied, inclu-

ding keypad zone 8.

Panel Hook-up Procedures

All panel wiring must be completed before connecting transformer or

battery. Install keypads and connect wires to keypad terminals on

panel. Bell or siren should be connected to "Bell+" and "Bell-" termi-

nals. Ensure correct polarity connection of sirens and pola-rized bells.

TERMINAL CONNECTIONS

AC Terminals

Use a 16VAC transformer with a minimum 40VA rating to provide

sufficient AC power. Do not utilize any switch-controlled outlets to

power the transformer.

Siren/Bell Terminals (Bell +, Bell -)

Bells or other warning devices requiring a steady voltage output

during alarms are powered by the bell relay and the bell output

(fused at 3A). Connect the positive lead to the "Bell+" terminal and

the negative lead to relay input "NO" or "NC". Also connect a wire

between Relay C terminal and "Aux-" terminal.

Auxiliary Power Terminals

Motion detectors and other security devices requiring 12VDC volt-

age can be powered by the auxiliary power supply. A maximum of

400mA 12VDC is available from the AUX+ and AUX- terminals

when only one keypad is used with the Esprit. For each additional

keypad the auxiliary supply must be reduced by 20mA. The auxil-

iary supply is fused at 1 amp. 

Keypad Terminal (RED, BLACK, YELLOW, GREEN)

Each keypad has connectors for four colored leads; red, black, yel-

low and green. Connect the lead to the corresponding colour input

terminal on the control panel and the keypad. Mount keypads near

entry/exit doors to shorten entry/exit delay intervals. If keypad zone

8 is to be used, connect it to the keypad with a 1KOHM EOL resis-

tor. If not, connect a 1KOHM EOL resistor in parallel to zone termi-

nals on keypad. Up to 5 keypads can be connected in parallel. 

Please note:

The keypad zone can be connected on all keypads

installed. However, any open keypad zones will always be indicated

as zone 8 on every keypad display. However, when keypad zone

supervision is enabled, only the zone that is supervised indicates a

zone 8 on every keypad. The keypad zone is always a delay zone.

Zone Input Terminals (z1 to z6, fire zone 7, keypad zone 8)

Zone terminals are the loop inputs for 6 fully-programmable

zones. Connect normally closed detectors or contacts to each

zone and jumper any unused loops with the EOL resistors sup-

plied. An open contact across the resistor or reduced loop resis-

tance in fire zone 7 will engage a pulse bell/siren. 

POWERING UP THE UNIT

When keypads are installed far from the control panel, we recom-

mend that you temporarily connect a keypad close to the panel to

conduct "power-up" testing. If key switches are being installed, a

keypad must be used to conduct programming.

Connect the transformer. After 5 seconds, you can begin testing

the unit. Enter random commands on the keypad. It should "beep"

in response to these commands.

Open a zone (except a keypad zone) to ensure that keypad and

panel are responding to signals. If the keypad does not respond

and if no indicator lights illuminate check for AC voltage at the

"AC" terminals. If 16VAC is flowing, then keypad wiring should be

verified, as well as the keypad/aux. supply fuse. If this fuse has

blown, check for a short between black and red keypad wires

before replacing it.

Battery Hook-up

Warning: Never connect the transformer or the battery until all

wiring has been completed. Use a 12VDC, 6.5 AH gel cell

battery. The red battery lead should be connected to the positive

battery terminal, and the black battery lead to the negative battery

terminal. Reversed connections will blow the battery fuse. The

battery should not be connected until AC connections to the panel

have been made. A "trouble" key indicator will illuminate on the

keypad if AC power is turned off and battery is connected.

SYSTEM STATUS COMMUNICATION

:

Every time a key is pressed, it illuminates and the keypad beeps

to show an entry has been recognized. There are two types of

beep tones which communicate information regarding keypad

entries to the system user.

"

CONFIRMATION

" beep: 

If an operation (ie. arming/disarming, programming) is correctly

entered on the keypad, or the system switches to a new

status/mode, the sounder emits an 

intermittent

beep tone.

"

END

/

REJECTION

" beep:

If the system reverts to previous status, or an operation is incorrect-

ly entered on the keypad, sounder emits a 

continuous

beep tone.

PROGRAMMING THE ESPRIT 727

Esprit system programming is performed from the keypad. The sys-

tem contains programmable memory (EEPROM) which does not

erase, even after total battery and AC loss. System automatically

reverts to "pre-power failure" status once battery/AC power are

restored. Please note: If system was "

armed

" prior to AC/battery

failure, it reverts to "armed" status approx. 2 minutes after power is

restored, to allow motion detectors sufficient time to warm up.

All programming pertaining to control panel operation is stored in

EEPROM sector which can only be accessed by entering the sys-

tem installer code. With the exception of the factory-set 

installer

code 0000 

and

master code 0101

, all other system features

8 ZONE SECURITY CONTROL PANEL

Installation Instruction Manual

Software Version 

3.3

1

INST727-970115-0001

Reviews: