OPERATING & MAINTENANCE MANUAL - 07/2016

JUNIOR V4

 - FIRE ALARM CONTROL PANEL

OPERATION & MAINTENANCE MANUAL

VERSION - 07/2016

JUNIOR V4

FIRE ALARM CONTROL PANEL

Summary of Contents for Junior V4

Page 1: ...ufacturers of Fire Detection Equipment globalfire pt OPERATING MAINTENANCE MANUAL 07 2016 JUNIOR V4 FIRE ALARM CONTROL PANEL OPERATION MAINTENANCE MANUAL VERSION 07 2016 JUNIOR V4 FIRE ALARM CONTROL PANEL ...

Page 2: ...ealarms 7 1 5 ReadtheFire Fault TestandDisabledqueues 8 1 6 ActiveDelays 9 1 7 LampTest 10 1 8 Performafiredrill 11 1 9 CaretakerTestMode 12 1 10 Disablements 14 1 10 1 Selecteddetectors 14 1 10 2 SoundersDisable 15 1 10 3 AuxiliaryRelays 15 1 10 4 Enable DisableZones 16 1 11 Ifthepaneldisplaysafault 16 1 12 Ifthepaneldisplaysapre alarm 16 2 1 SIMCARD replacement 17 2 2 ReplacingtheElectricalMains...

Page 3: ...he LED is flashing GREENthenthepanelisinINSTALLATIONmode ZONES ZONES FireZoneindicatorLEDs 1 1 DESCRIPTION OF THE FIRE CONTROL PANEL FASCIA QUEUE REVIEW FAULTS KEYPAD CONTROLS DISABLEMENTS FIRE FAULT PRE ALARM TEST DISABLED SYSTEM ON ALARM FAULT SUPPLY FAULT SYSTEM FAULT DISABLED TEST FAULT FIRE 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 FIRE ALARM CONTROL PANEL ENTER ESC DELAYS ACTIVE SELECTED DETECT...

Page 4: ...tton to confirm the LEDs and LCDdisplayarefunctional SOUNDERS Pressing this button will activate all sounders and panel buzzers main panel and Repeaters Pressing the button again will silence the sounders If the LED is RED it means that the SOUND ALARMS function has been activated by either pressing SOUNDERS ACTIVATE SILENCE switch or during an alarm or Evacuate function is active DISABLEMENTS AUX...

Page 5: ...ere are ZONES in test mode then pressing this button will show those ZONES on the LCD display If more ZONES are in test mode than can be shown on the LCD display at one time then subsequent presses of the button will step through all the ZONES in test mode If the LED is AMBERit means thatone or more ZONES are in test mode DISABLED If there are disablements then pressing this button will show the d...

Page 6: ...nal buzzer turn off BUZZER SILENCE LED To stop Sounders press SOUNDER ACTIVATE SILENCE button The LED will also turn off after pressing The STATUS FIRE LED will remain lit RED The STATUS FIRE LED will illuminate RED The fire control panel buzzer will sound continuously The location of the alarm or alarms will be shown on the fire control panel LCD display 1 2 ALARM AuthorizedUserAccess Ifthefireal...

Page 7: ...NDERS ACTIVATE SILENCE button All sounders turn on The SOUNDERS ACTIVATE SILENCE LED illuminates RED To stop sounders press SOUNDERS ACTIVATE SILENCE button again The SOUNDERS ACTIVATE SILENCE LED extinguishes 1 4 SOUND AND SILENCE THE ALARMS EVACUATION Authorized User Access This section shows you how to turn on and turn off all the sounders in an installation It is identical to a fire drill proc...

Page 8: ...nceallmessageshavebeendisplayed After20secondsthefirstfireeventwillbere displayed A B C D A B C D FAULT IftheQUEUEREVIEW FAULTLEDisflashingAMBER Press the QUEUE REVIEW FAULT button to display the first queued message Press the button again to review the next queued message Do this until all messages have been reviewed The LED illuminates steady AMBER when all messageshavebeendisplayed After 20 sec...

Page 9: ...delays are only active when the DELAYS ACTIVE LED is illuminated At all other times the sounders and I O moduleswilloperateimmediatelywhen ifafireisdetected AfterenteringUserAccesscode toenableordisablethesedelayspresstheDELAYSACTIVESbutton Notethatitisalsopossible viatheprogrammingfunctions tosetDELAYSACTIVEtoautomaticallyturnoffatnight Fordetailsontheprogrammablefeaturesanddelaysrefertothe Insta...

Page 10: ...F EN54 2 EN54 4 CERTIFIED 1328 CPR 0179 STATUS ZONES PressandholdtheLAMPTESTbutton AllLEDsshowninthisdiagramshouldbeilluminated AllpixelsontheLCDdisplayshouldturnblack AllexternalZoneLEDsshouldbeilluminated Release the LAMP TEST button to end the test The LEDs and LCD display will return to their normalcondition 1 7 LAMP TEST General User Access This tests that all LEDs on the fascia are functioni...

Page 11: ... EN54 4 CERTIFIED 1328 CPR 0179 STATUS ZONES A A 1 8 PERFORM A FIRE DRILL Access Level 2 or Authorized User Access To end the fire drill press the SOUNDERS ACTIVATE SILENCE button The following will occur The sounders stop sounding The SOUNDERS ACTIVATE SILENCE LED extinguishes To start the fire drill press the SOUNDERS ACTIVATE SILENCE button The following will occur All sounders turn on The SOUN...

Page 12: ...llation Mode When Caretaker Test Mode is entered INITIALIZING may be displayed for up to 20 seconds depending on the system size Caretaker Test Mode is exited by pressing SYSTEM RESET Indication of Caretaker Test Mode The TEST LED will be lit The buzzer will sound for 0 5 seconds every 5 seconds same as FAULT indication ALARM SILENCE will not stop this The message DETECTOR TEST MODE will be displa...

Page 13: ...Device Detectors and callpoints can only be tested one at a time The LED must be extinguished on the current device before moving on to test the next device Don t use too much smoke spray Disablements All disablements for sounders loop and detectors are ignored during Caretaker Test Mode However the LED on disabled detectors will not be lit when the detector is tested all other aspects of the test...

Page 14: ...CPR 0179 STATUS ZONES 1 10 DISABLEMENTS Authorized User Access 1 10 1 SELECTED DETECTORS SELECTED DETECTORS When activated The SELECTED DETECTORS LED will be illuminated The STATUS DISABLED LED will be illuminated The QUEUE REVIEW DISABLED LED will be illuminated The disabled detectors can be reviewed using the DISABLED QUEUE REVIEW button Using the programming functions see the Installation Commi...

Page 15: ... B A D A B C D A B C 1 10 2 SOUNDERS DISABLE To disable the relay and I O module outputs press the AUXILIARY RELAYS button The AUXILIARY RELAYS LED illuminates AMBER The STATUS DISABLED LED illuminates AMBER The QUEUE REVIEW DISABLED LED illuminates AMBER Re press the AUXILIARY RELAYS button to re enable the relays and I O modules 1 10 3 AUXILIARY RELAYS The AUXILIARY RELAYS DISABLEMENT button ena...

Page 16: ...TER 5 The present status of the zone is shown To change it press ENTER and change the status using the p q arrow keys from enabled to disabled and vice versa When selection is complete press OK Enter ToexitpresstheESCkey EachconsecutivepressoftheESCkeywillrevertbackonestep If any zones are disabled during this time the DISABLED LED in the STATUS area of the panel s fascia will be lit The DISABLED ...

Page 17: ...e released position push the SIM CARD forward and down until it is almost horizontal with the main panel board Lift the SIM CARD off the connector To install the replacement SIM CARD locate it on the connector almost horizontally with the main panel board push it up and back gently until the retaining clips snap into position Download the panel configuration from the PC if SIM is not pre programme...

Page 18: ...gcorrectly Notethattousethesefunctionstheinstallerneedstohavegranted UserAccess tothefollowingfunctions By default accessisdenied 1ReviewHistoricLog Allthefunctionsassociatedwithreviewing eventsandsettings 1 1DisplayHistoricLog The panel logs all events in an internal event log It can store a rolling 2000 entries When it is full the latest entryisaddedandtheoldestentrydiscarded Help is automatical...

Page 19: ...sounder operation The settings selected by thisfunctionareusedby 7 4TestZones and 6 4 1ActivateASETMode SAM ALLSOUNDERSONDETECTORTESTactivatesthePanelConventionalandLoopSounders NOTE using this function AFTER 7 4 Test Zones and 6 4 1 Activate ASET Mode SAM will NOT changethesettingsforthezonesalreadyintestmodeandtheloopsalreadyinASETmode 7 4TestZones Select the Zones you wish to put into test mode...

Page 20: ...s Levels You have unlimited attempts but if code entry is not started within 10 seconds then the panel will revert back to its default screen While entering the code you are allowed up to 5 seconds between key presses Function Selection The programming functions are arranged using a menu system To select a function or sub menu use either pq and ENTER ESC takes you up a menu level The top level men...

Page 21: ...d can be photocopied to produce a logbook that conforms to EN54 14 The sample below is for the reference data e g the name of the responsible person whilst the sample onthenextpageisforentryofeventdata REFERENCE DATA Name and address Responsible person Date _________________________ ________________________ Date _________________________ ________________________ Date _________________________ ____...

Page 22: ...ATE TIME EVENT INITIALS ACTION REQUIRED DATE COMPLETED 2 7 EVENT DATA SHEET Manufacturers of Fire Detection Equipment globalfire pt OPERATING MAINTENANCE MANUAL 07 2016 JUNIOR V4 FIRE ALARM CONTROL PANEL ...

Page 23: ...ANCE MANUAL 07 2016 JUNIOR V4 FIRE ALARM CONTROL PANEL GLOBAL FIRE EQUIPMENT S A Sítio dos Barrabés Armazém Nave Y Caixa Postal 908 Z 8150 016 São Brás de Alportel PORTUGAL Tel 351 289 896 560 Sales sales globalfire pt Technical Support techs globalfire pt www globalfire pt ...