FAULTS
ALARM FAULT
If the LED is AMBER it indicates that there is a problem with a loop sounder or
conventional sounder circuit. This could be an open or short circuit.
SUPPLY FAULT
If the LED is AMBER it indicates that there is a Primary Supply (Electrical mains) Fault,
a Battery Fault or that there is an Earth Fault.
SYSTEM FAULT
If the LED is AMBER it indicates that there is 5 Volt fault or a processor/program
failure.
KEYPAD
KEYPAD
Press these buttons to toggle between menus, enter User and programming codes
and other on-screen information.
CONTROLS
BUZZER SILENCE
Pressing this button will silence the internal buzzer during a FIRE or FAULT condition.
If the LED is lit, it indicates that a new FAULT or FIRE condition has occurred.
SYSTEM RESET
Pressing this button restores the panel to its normal operating condition after an
alarm. Alarms must be silenced before a SYSTEM RESET can be performed. A
SYSTEM RESET does not clear any settings or disablements; it only clears FIRE and
FAULT conditions (and then only if the source of the FIRE or FAULT has been cleared).
LAMP TEST
Whilst this button is depressed all of the panel’s LEDs will be illuminated and all of
the LCD display pixels will be set to black. Use this button to confirm the LEDs and
LCD display are functional.
SOUNDERS
Pressing this button will activate all sounders and panel buzzers (main panel and
Repeaters). Pressing the button again will silence the sounders. If the LED is RED it
means that the SOUND ALARMS function has been activated by either pressing
SOUNDERS ACTIVATE/SILENCE switch or during an alarm or Evacuate function is
active.
DISABLEMENTS
AUXILIARY RELAYS
Pressing this switch disables or enables all the relay and I/O module outputs. If the
LED is lit it means that the relay and I/O module outputs are disabled.
DELAYS ACTIVE
Delays can be configured for the sounders and I/O modules using the programming
functions. Pressing this button enables or disables these delays. If the LED is AMBER
it means that the delays are active.
SOUNDERS DISABLE
Pressing this button will enable/disable all sounders in the system. The LED will be lit
when sounders are disabled.
SELECTED DETECTORS Using the programming functions individual detectors can be set for SELECTIVE
DISABLEMENT. When this button is activated those detectors will be disabled
(isolated). Note that this button will only operate if at least one detector has been set
for SELECTIVE DISABLEMENT. If the LED is AMBER it means that the selected
detectors are isolated.
ACTIVATE/SILENCE
Manufacturers of Fire Detection Equipment