If any detector detects a pre-alarm condition, the
STATUS - PRE-ALARM LED will light up AMBER.
FOLLOW SITE SPECIFIC INSTRUCTIONS
1.12 IF THE PANEL DISPLAYS A PRE-ALARM
If the system detects a fault, the STATUS - FAULT LED
will light up AMBER.
CALL THE MAINTENANCE ENGINEER
1.11 IF THE PANEL DISPLAYS A FAULT
1.10.4 ENABLE / DISABLE ZONES
In order to Enable/Disable a zone follow the procedure described below:
1 -
Enter either a valid User or Programming Code.
2 -
Select Function 3.1 (Zones Disable/Assign), using the
p
q
arrow keys. Press ENTER when menu
3 is reached.
3 -
Using the
p
q
arrow keys once more, select function 3.1 and press ENTER.
4 -
Select the zone to be disabled using the
p
q
arrow keys and press ENTER.
5 -
The present status of the zone is shown. To change it, press ENTER and change the status using
the
p
q
arrow keys from enabled to disabled and vice versa. When selection is complete press
OK/Enter. To exit press the ESC key. Each consecutive press of the ESC key will revert back one step.
If any zones are disabled during this time, the DISABLED LED in the STATUS area of the panel's fascia
will be lit. The DISABLED LED in the QUEUE REVIEW area will also be lit. If the latter LED flashes, this
gives the indication that more than one disblement has taken place in the system. To scroll through
these multiple disablements, press the DISABLED button in the QUEUE REVIEW area.
B
A
STATUS
FIRE
FAULT
PRE-ALARM
TEST
DISABLED
SYSTEM ON
A
B
Manufacturers of Fire Detection Equipment
globalfire.pt
OPERATING & MAINTENANCE MANUAL - 07/2016
JUNIOR V4
- FIRE ALARM CONTROL PANEL