QUEUE REVIEW
FIRE
If there is more than one FIRE pressing this button will display the next FIRE report on
the LCD display for 20 seconds. Subsequent presses will step through all the FIRE
reports. If the LED is flashing RED it means that there are FIRE reports to be reviewed.
If the LED is steady RED then all FIRE reports have been reviewed.
FAULT
If there is more than one FAULT, or if there is at least one FAULT and a FIRE, pressing
this button will display the next FAULT report on the LCD display for 20 seconds.
Subsequent presses will step through all the FAULT reports. If the LED is flashing
AMBER it means that are FAULT reports to be reviewed. If the LED is steady AMBER
then all FAULT reports have been reviewed.
TEST
If there are ZONES in test mode then pressing this button will show those ZONES on
the LCD display. If more ZONES are in test mode than can be shown on the LCD
display at one time then subsequent presses of the button will step through all the
ZONES in test mode. If the LED is AMBER it means that one or more ZONES are in test
mode.
DISABLED
If there are disablements then pressing this button will show the disablements on
the LCD display. If there are more disablements than can be shown on the LCD
display at one time then subsequent presses of this button will step through all the
disablements. If the LED is AMBER it means that there is at least one disablement.
NOTE:
The functions of some switches will only be operational after entering the authorized user or
programming access codes.
Manufacturers of Fire Detection Equipment
globalfire.pt
OPERATING & MAINTENANCE MANUAL - 07/2016
JUNIOR V4
- FIRE ALARM CONTROL PANEL