53DS−900−−−091

Installation  Instructions

Duct−Free Systems

Wired Room Controller

Cooling Only and Heat Pump High−Wall Units

(Sizes  018−036)

NOTE

:  Read and become familiar with these instructions before

beginning installation.

SAFETY CONSIDERATIONS

Installing and servicing air

conditioning equipment can be

hazardous due to system pressures and electrical components.

Only trained and qualified personnel should install or service

air

conditioning equipment. When working on air

conditioning

equipment, observe the precautions provided in literature, tags,

and labels attached to the unit.
Follow all safety codes. Wear safety glasses, protective clothing,

and work gloves. Use quenching cloth for brazing operations.

Have fire extinguisher available. Read these instructions

thoroughly and follow all warnings or cautions included in

literature and  attached to the unit. Consult local building codes

and National Electrical Code (NEC) for special requirements.

Recognize safety information. This is the safety

alert symbol 

!

 
!

.

When you see this symbol on the unit and in instructions or

manuals, be alert to the potential for personal injury.
Understand these signal words: DANGER, WARNING, and

CAUTION. These words are used with the safety

alert symbol.

DANGER identifies the most serious hazards which 

will 

result in

severe personal injury or death.   WARNING signifies hazards

which 

could

 result in personal injury or death. CAUTION is used

to identify unsafe practices which 

may 

result in minor personal

injury or product and property damage. NOTE is used to

highlight suggestions which 

will

 result in enhanced installation,

reliability, or operation.

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury

or death.
Before beginning any modification or installation of this kit,

be sure the main electrical disconnect is in the OFF position.

Ensure power is disconnected to the fan coil unit. On some

systems both the fan coil and the outdoor unit may be on the

same disconnect. Tag the disconnect switch with a suitable

warning label. There may be more than one disconnect.

!

WARNING

GENERAL

The wired remote controller is used with the 40BNC
High−Wall fan coil units which use microprocessor control.
The remote controller is directly wired to the fan coil by an
interconnecting cable provided. Temperature sensing is done
at the fan coil unit, so the wall controller may be located
anywhere  within 9 ft. of the unit.
The remote controller provides an interface with the unit to:

S

Change set points

S

Set timer

S

Start and stop unit

S

Display operating status of unit

S

Display fault codes should a problem occur.

Refer to Table 1 and Fig. 1 for a list of parts included in this
kit.

Table 1—Wired Remote Controller Kit Contents

Item

Quantity

RTX Wired Remote Controller

1

Display Cable

9 ft.

Attachment Screws

2

Anchors

2

Wall Control Circuit Board

1

Display Cable 
9.2 ft in Length

Room Controller Unit 
                (RTX)  

Wall Control 
Circuit Board

A06468

Fig. 1

 − 

Kit Contents

INSTALLATION OF WIRED ROOM CONTROLLER

1. Select a location to mount the wall controller. 

Since the wall controller is not used to sense temperature,

it should be placed in a location that is easily accessible

when changing settings and at a height where the display

can be easily seen (approximately 5 ft. above the floor and

within 9 ft. of the fan coil.)

2. Take the Room Controller (RTX) out of its packaging.
3. Mount the control on the wall, taking into account the

length of available cable (9 ft.).

NOTE

:  

Common phone cable will not replace the cable

provided with the kit.

4. Connect the display unit cable to the RTX display unit

(see Fig. 2).

Summary of Contents for 40BNC

Page 1: ...in personal injury or death Before beginning any modification or installation of this kit be sure the main electrical disconnect is in the OFF position Ensure power is disconnected to the fan coil unit On some systems both the fan coil and the outdoor unit may be on the same disconnect Tag the disconnect switch with a suitable warning label There may be more than one disconnect WARNING GENERAL The...

Page 2: ... Ensure power is disconnected to the fan coil unit On some systems both the fan coil and the outdoor unit may be on the same disconnect Tag the disconnect switch with a suitable warning label There may be more than one disconnect WARNING 5 Remove the front grille see Fig 3 A06470 Fig 3 Remove Front Grille 6 Carefully close the louvers 7 Remove the two screws from the electrical box cover See Fig 4...

Page 3: ...tor to its original location Additional display card connection previously hidden A06475 Fig 8 Threading Display Cable 22 Insert the end of the new display unit cable into the socket located underneath the wall control adapter circuit board see Fig 8 23 Insert the ends of the two wiring harnesses into the existing connectors located in upper part of the Display Adapter Card see Fig 8 24 Press down...

Page 4: ...mplete check as instructed in the attached operating manual Check the changes between operating modes changes in fan speed settings temperatureadjustments etc 2 If necessary the display can be changed from degrees Celsius to degrees Fahrenheit details in the operating manual 3 If the complete check reveals any malfunctions refer to the troubleshooting table in the operating manual 4 If the air con...

Reviews: