TH1
TH2
TH3

1

2

3

4

6/N

7*

Inter-unit

cable

Inter-unit

cable clamp

Power

cable

Power

cable

clamp

Screw attaching the

controller to the air-

conditioning unit

THI, TH2 and TH3

sensor connections to

the control unit

A06473

Fig. 6

 − 

Control Unit

13. Use a screwdriver to release the end of the inter

unit cable

from its connectors (see Fig. 6).

14. Use a screwdriver to release the power cable ends from the

connectors (see Fig. 6).

15. Use a screwdriver to release the inter

unit cable from its

clamp.

16. Use a screwdriver to release the power cable from its

clamp.

17. Remove the TH1, TH2, and TH3 sensors from their

connection locations in the unit (see Fig. 6).

18. Pull the controller slightly outwards.
19. Disconnect the existing display card connections 

(see Fig. 7.)

TH1
TH2
TH3

Display

Card

connector

Card gripping tabs

A06474

Fig. 7

 − 

Wall Control Adapter

20. Open the gripping tabs on each side and remove the

existing display card from its socket (see Fig. 7).

21. Thread the new display cable (included in the kit) through

the rear of the air

conditioner (adjacent to the entry for the

inter

unit cable) and through the space underneath the

display card (see Fig. 8).

TH1
TH2
TH3

Back of new card:

Insertion of the display

cable into the display

socket.

Return the display

connector to its

original location

Additional display

card connection;

previously hidden.

A06475

Fig. 8

 − 

Threading Display Cable

22. Insert the end of the new display unit cable into the socket

located underneath the wall control adapter circuit board

(see Fig. 8).

23. Insert the ends of the two wiring harnesses into the

existing connectors located in upper part of the Display

Adapter Card (see Fig. 8).

24. Press down gently on the wall control adapter circuit

board to insert it into its proper position (to make this

easier, open the tabs on each side of the cardholder (see

Fig. 7).

DIPSWITCH SETTINGS

TH1
TH2
TH3

1

2

3

4

6/N

7*

1 2 3 4 5 6

ON

1 2 3 4 5 6

ON

1 2 3 4 5 6

ON

Controller

Lower right side of

the controller

Move DIP

switch 4 to the

OFF position.

A06477

Fig. 9

 − 

Dipswitch Settings

NOTE

:  Only dipswitch 4 should be changed. All other switches

should remain in the position as shown on the sticker on the back
of the control unit.

1. Changes must be made to the position of dipswitch 4 in

the indoor unit’s control box to allow the air conditioner to

be operated by RTX room display unit fixed to the wall.

2. Remove the control box to permit access to the

dipswitches located in the lower part of the control box.

3. Move dipswitch number 4 to the OFF position
4. Replace the control back in its proper position 

(see Fig. 9).

5. Reinstall control box and all connecting wires by

reversing steps 3 through 15 in the Installation section of

the display card.

53DS

900

−−−

091

Summary of Contents for 40BNC

Page 1: ...in personal injury or death Before beginning any modification or installation of this kit be sure the main electrical disconnect is in the OFF position Ensure power is disconnected to the fan coil unit On some systems both the fan coil and the outdoor unit may be on the same disconnect Tag the disconnect switch with a suitable warning label There may be more than one disconnect WARNING GENERAL The...

Page 2: ... Ensure power is disconnected to the fan coil unit On some systems both the fan coil and the outdoor unit may be on the same disconnect Tag the disconnect switch with a suitable warning label There may be more than one disconnect WARNING 5 Remove the front grille see Fig 3 A06470 Fig 3 Remove Front Grille 6 Carefully close the louvers 7 Remove the two screws from the electrical box cover See Fig 4...

Page 3: ...tor to its original location Additional display card connection previously hidden A06475 Fig 8 Threading Display Cable 22 Insert the end of the new display unit cable into the socket located underneath the wall control adapter circuit board see Fig 8 23 Insert the ends of the two wiring harnesses into the existing connectors located in upper part of the Display Adapter Card see Fig 8 24 Press down...

Page 4: ...mplete check as instructed in the attached operating manual Check the changes between operating modes changes in fan speed settings temperatureadjustments etc 2 If necessary the display can be changed from degrees Celsius to degrees Fahrenheit details in the operating manual 3 If the complete check reveals any malfunctions refer to the troubleshooting table in the operating manual 4 If the air con...