Chapter 3: Initial Installation and Configuration
43
For instructions on USB cascading, see
Cascading PX3 via USB
(on page
Suggestions for extended cascading:
Ethernet cascading is recommended because of the longer distance,
lower latency and more reliable connection it supports.
The 'green' ETH1 port (ETH 10/100/1000) of the master device is
recommended for network connection because it supports up to
1000 Mbps.
To cascade iX7
™
PDUs via Ethernet ports:
1.
Make sure all Raritan devices are running firmware version 3.3.10 or
later.
2.
Choose one iX7
™
PDU as the master device.
3.
Log in to all devices one by one and select the same cascading mode.
Bridging mode:
Set the cascading mode of all devices to Bridging.
Port Forwarding mode:
Set the cascading mode of all devices to Port Forwarding. Make
sure the cascading role and downstream interface are also set
correctly.
See
Setting the Cascading Mode
(on page 265).
4.
Connect the master device to the LAN, using a method below.
Bridging mode:
Use a standard network patch cable (CAT5e or higher).
Port Forwarding mode:
Use a standard network patch cable and/or a Raritan USB WIFI
wireless LAN adapter. For information on the Raritan USB WIFI
adapter, see
USB Wireless LAN Adapters
(on page 24).
5.
Connect the available Ethernet port of the master device to either
Ethernet port of another iX7
™
via a standard network patch cable.
This additional iX7
™
device is Slave 1.
6.
Connect Slave 1's available Ethernet port to either Ethernet port of
another iX7
™
via a standard network patch cable. The second
additional device is Slave 2.
7.
Repeat the same step to connect more iX7
™
devices. You can cascade
up to 15 slave devices.
8.
(Optional) Configure or change the network settings of the master
and/or slave devices as needed. See
Configuring Network Settings
(on page 251).
Содержание PX3-3000 series
Страница 5: ......
Страница 18: ...Contents xviii Index 841...
Страница 66: ...Chapter 3 Initial Installation and Configuration 42 Number Device role Master device Slave 1 Slave 2 Slave 3...
Страница 93: ...Chapter 4 Connecting External Equipment Optional 69...
Страница 787: ...Appendix J RADIUS Configuration Illustration 763 Note If your PX3 uses PAP then select PAP...
Страница 788: ...Appendix J RADIUS Configuration Illustration 764 10 Select Standard to the left of the dialog and then click Add...
Страница 789: ...Appendix J RADIUS Configuration Illustration 765 11 Select Filter Id from the list of attributes and click Add...
Страница 792: ...Appendix J RADIUS Configuration Illustration 768 14 The new attribute is added Click OK...
Страница 793: ...Appendix J RADIUS Configuration Illustration 769 15 Click Next to continue...
Страница 823: ...Appendix K Additional PX3 Information 799...
Страница 853: ...Appendix L Integration 829 3 Click OK...