Appendix K: Additional PX3 Information
803
Threshold
Default value
Upper warning
65% of OCP rating
Hysteresis 1A
Residual current:
Threshold
Default value
Upper critical
30mA
Hysteresis 15mA
Altitude Correction Factors
If a Raritan differential air pressure sensor is attached to your device,
the altitude you enter for the device can serve as an altitude correction
factor. That is, the reading of the differential air pressure sensor will be
multiplied by the correction factor to get a correct reading.
This table shows the relationship between different altitudes and
correction factors.
Altitude (meters)
Altitude (feet)
Correction factor
0 0 0.95
250 820 0.98
425 1394
1.00
500 1640
1.01
740 2428
1.04
1500 4921 1.15
2250 7382 1.26
3000 9842 1.38
Содержание PX3-3000 series
Страница 5: ......
Страница 18: ...Contents xviii Index 841...
Страница 66: ...Chapter 3 Initial Installation and Configuration 42 Number Device role Master device Slave 1 Slave 2 Slave 3...
Страница 93: ...Chapter 4 Connecting External Equipment Optional 69...
Страница 787: ...Appendix J RADIUS Configuration Illustration 763 Note If your PX3 uses PAP then select PAP...
Страница 788: ...Appendix J RADIUS Configuration Illustration 764 10 Select Standard to the left of the dialog and then click Add...
Страница 789: ...Appendix J RADIUS Configuration Illustration 765 11 Select Filter Id from the list of attributes and click Add...
Страница 792: ...Appendix J RADIUS Configuration Illustration 768 14 The new attribute is added Click OK...
Страница 793: ...Appendix J RADIUS Configuration Illustration 769 15 Click Next to continue...
Страница 823: ...Appendix K Additional PX3 Information 799...
Страница 853: ...Appendix L Integration 829 3 Click OK...